CCR-23 Rectifier Controller Communication Driver is the driver to communicate with rectifier controller of WonBang C & C in Korea.
<Figure 1> is read setting example of CCR-23 Rectifier Controller communication driver.
<Figure 1> Read setting example of CCR-23 Rectifier Controller communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(57600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively.
CCR-23 Rectifier Controller Indicator communication driver¡¯s read schedule
Read schedule setting parameters are as follows:
1) STATION – Controller ID = 0 ~ 255.
2) Read command – Don't care(input blank).
3) Read start address – Don't care.
4) Save start address for Communication Server – Saving start address of Communication Server.
Start Addr + 0 : Version(Fixed to 2),
Start Addr + 1 : Flag( Refer to <Table 1> ),
Start Addr + 2 : Error(( Refer to <Table 2> ),
Start Addr + 3 : Voltage(real value = read value / 10),
Start Addr + 4 : Current(real value = read value / 10),
Start Addr + 5 : Voltage(set, real value = read value / 10),
Start Addr + 6 : Current(set, real value = read value / 10),
Start Addr + 7 ~ 12 : Setup 1 ~ 6.
5) Read Size – Size = Fix to 1. ( Refer to <Table 1> )
Read schedule example)
READ, 3 , , 0, 0, 1,
<Table 1> is a description of Meaning for each bit of 'Flag' value. <Table 2> is a description of Meaning for each bit of 'Error' value.
bit position | Meaning |
15 (8000h) | ON = Communication error or controller turn off OFF = Normal |
14~8 | - |
7 (80h) | ON = RUN, OFF = STOP |
6 (40h) | ON = SETUP, OFF = RUN/STOP |
5 (20h) | |
4 (10h) | ON = Error, OFF = None ERROR |
3 ~ 1 | - |
0 (01h) | ON = time set OK, OFF = don't time set |
<Table 1> Meaning for each bit of 'Flag' value |
bit position |
Meaning |
15 ~ 13 |
- |
12 (1000h) |
Over Voltage |
11 (0800h) |
Over Current2 |
10 (0400h) |
Over Current1 |
9 ~ 7 |
- |
6 (40h) |
Controller Error |
5 (20h) |
Over Temperature |
4 (10h) |
Fuse Open |
3 (08h) |
Wire Fault |
2 ~ 1 |
- |
0 (01h) |
Offset Fail |
<Table 2> Meaning for each bit of 'Error' value |
If you click the icon in protocol option part, you can see the dialogue box such as <Figure 2>. you can also set read schedule by using this part.
<Figure 2> Example of CCR-23 Rectifier Controller communication driver¡¯s Option dialogue box |
You can set read schedule by using , , button and listbox of <Figure 2>.
<Figure 3> Example of CCR-23 Rectifier Controller communication driver¡¯s read schedule Add/Edit dialogue box |
When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.
CCR-23 Rectifier Controller communication driver don't support writing settings because of read only controller.
Please connect 2, 3, 4, 5( from left 1, 2, .... ) connector of RJ11 RS-485 and Rx-, Rx+, Tx-, Tx+ connector of computer's RS-485.
CCR-23 side computer side
2 ----------------------------- Rx-
3 ----------------------------- Rx+
4
-----------------------------
5
-----------------------------
<Figure 4> is appearance of CCR-23 Rectifier Controller.
<Figure 4> Appearance of CCR-23 Rectifier Controller |