SIEMENS LOGO Learn Module Communication Driver

 

GIEMENS LOGO Learn Module is driver to communicate with LOGO instructional device of SIEMENS Corp., in Germany.

 

1. Read settings

 

<Figure 1> is read setting example of GIEMENS LOGO Learn Module communication driver.

<Figure 1> Read setting example of GIEMENS LOGO Learn Module driver

Device part of  <Figure 1> input Com Port(COM3), Baud Rate(9600), Parity Bit(1), Data Bit(8), Stop Bit(1) respectively, according to device.

 

SIEMENS LOGO Learn Module driver's read schedule

Read schedule setting parameters are as follows:

1) STATION – Don't care.

2) Read Command – Fixed to READ(or Blank).

3) Read Start Address – Don't care.

4) Save Start Address for Communication Server - Saving start address of Communication Server.

5) Read Size – Always fixed to 1.

 

Read schedule example)

READ,     0,  READ,     0,    0,   1,

 

<Table 1> is save address of read value and contents for GIEMENS LOGO Learn Module driver's read command( READ ). 

Save address of Read value

Remarks

Save addr + 0  : Digital input value( I )

Save addr + 1  : Digital output value( I )

Save addr + 2  : Analog input value( AI1 )

Save addr + 3  : Analog input value( AI2 )

0 ~ 7 bit = I0 ~ I7

0 ~ 3 bit = O0 ~ O3

Value between 0 and 1000

Value between 0 and 1000

<Table 1> Save address of read value and contents for GIEMENS LOGO Learn Module driver's read command( READ )

Notice) Read value is saved at WORD/DWORD/FLOAT/STRING memory as same value( value type is only different ).

 

If you click the icon 2 in protocol option part at <Figure 1>, you can see the dialog box such as <Figure 2>. You can also set read schedule by using this part.

<Figure 2> Example of GIEMENS LOGO Learn Module communication driver's Option dialog box

You can set read schedule by using 3, 4, 5 button and listbox of <Figure 2>.

When you click Add button or Edit button in dialog box of <Figure 2>, dialog box of <Figure 3> is shown.

<Figure 3> Example of GIEMENS LOGO Learn Module communication driver's Add/Edit dialog box
2. Writing settings

 

There is no writing settings for GIEMENS LOGO Learn Module communication driver.