SR90 Series Digital Controller is driver to communicate with controller of Shimaden Co., Ltd, in Japan.
<Figure 1> is read setting example of SR90 Series Digital Controller communication driver.
<Figure 1> Read setting example of SR90 Series Digital Controller communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(2), Data Bit(7), Stop Bit(1) respectively, according to device.
Also, you can enter BCC format(0 = No BCC, 1 = SUM, 2 = Two's complement, after SUM, 3 = XOR, Default : 3) set at device, Start/End code format of protocol(0 = STX/ETX, 1 = ATT(40h, 3Ah), Default :1) by classifying as comma(,).
SR90 Series Digital Controller communication driver's read schedule
Read schedule setting parameters are as follows :
1) STATION – Enter device address between 1 and 99. (Usually, value between 1 and 31)
2) Read Command – Enter READ command.
3) Read Start Address – Data start address to read. (Refer to <Table 1>)
Enter number as decimal or hexadecimal. In case of hexadecimal, enter 'h' at end of number.
4) Save start address for Communication Server – Saving start address of Communication Server.
5) Read Size - Number of data size to read. Enter between 1 and 10.
Read schedule example)
READ, 1, READ, 100h, 0, 6,
<Table 1> is main data address and contents of SR90 Series Digital Controller communication driver.
Main Data Address |
Parameter |
Contents |
Remarks |
100h | PV_W |
Measured Value |
Each data value uses WORD unit. |
101h | SV_W |
SV Value in Execution |
|
102h | OUT1_W |
Control Output 1 Value |
|
103h | OUT2_W |
Control Output 2 Value(without option = 0000h) |
|
104h | EXE_FLG |
Action Flag(bit without action = 0) |
|
105h | EV_FLG |
Event Output Flag(without option = 0000h) |
|
<Table 1> Main data address and contents of SR90 Series Digital Controller communication driver |
Refer to 'Communication Interface' Instruction Manual of SR-90 Series about detailed data address and contents of SR90 Series Digital Controller communication driver.
Read value of SR90 Series Digital Controller communication driver is saved at WORD/DWORD/FLOAT memory as same value(Only, save format is different).
If you click the icon in protocol option part at <Figure 1>, you can see the dialog box such as <Figure 2>. you can also set read schedule by using this part.
<Figure 2> Example of SR90 Series Digital Controller driver's Option dialog box |
You can set read schedule by using , , button and listbox of <Figure 2>.
Also, you can set BCC type and Start/End code format of protocol(which is set at device) at 'BCC Type', 'Start/End Code Type' part of <Figure 2>.
<Figure 3> Example of SR90 Series Digital Controller driver's read schedule Add/Edit dialog box |
When you click Add button or Edit button in dialog box of <Figure 2>, dialog box of <Figure 3> is shown.
You can setting value of SR90 Series Digital Controller by using writing setting.
Digital Write
Digital write and analog write have the same setting parameters except output value(0 or 1).
Analog Write
Analog write setting parameters are as follows :
1) PORT Connected port number. (Not COM number)
2) STATION Enter device address between 1 and 99. (Usually, value between 1 and 31)
3) ADDRESS Enter data address to output as hexadecimal.
4) Extra1 Enter WRITE command.
5) Extra2 Don't care.
Write example 1)
PORT : 0 STATION : 1 ADDRESS : 0300 EXTRA1 : WRITE EXTRA2 : 0
If you set as above and writing analog value, you can change SV1 of no.1 SR90 Series device connected no.0 port as set value.
Write example 2)
PORT : 0 STATION : 1 ADDRESS : 0400 EXTRA1 : WRITE EXTRA2 : 0
If you set as above and writing analog value, you can change PB1 of no.1 SR90 Series device connected no.0 port as set value.
Block Write
There is no Block Write for SR90 Series Digital Controller.