In case of selecting SATEC RPT091 driver's communication protocol as ASCII(Open PROT terminal), save contents and address by read/write type are as follows.
Memory Save Address | Contents | Unit | Range |
Save Addr + 0 ~ 2 | L1~L3/L12 ~ L31 Voltage | V/KV | 0 ~ Vmax |
Save Addr + 3 ~ 5 | L1 ~ L3 Current | A | 0 ~ Imax |
Save Addr + 6 ~ 8 | L1 ~ L3 Watt(KW) | KW/MW | -Pmax ~ Pmax |
Save Addr + 9 ~ 11 | L1 ~ L3 Power Factor | - | -0.99 ~ 1 |
Save Addr + 12 | KW Total | KW/MW | -Pmax ~ Pmax |
Save Addr + 13 | Power Factor Total | - | -0.99 ~ 1 |
Save Addr + 14 | KWh Import | KWh/MWh | 0 ~ 99999 |
Save Addr + 15 | Neutral (Unbalanced) Current | A | 0 ~ Imax |
Save Addr +16 | Frequency | HZ | 45 ~ 65 |
Save Addr + 17 ~ 19 | L1 ~ L3 Kvar | Kvar/Mvar | -Pmax ~ Pmax |
Save Addr + 20 ~ 22 | L1 ~ L3 KVA | KVA/MVA | -Pmax ~ Pmax |
Save Addr + 23 | Kvarh net | Kvarh/Mvarh | -9999.9 ~ 99999 |
Save Addr + 24 | Kvar total | Kvar/Mvar | -Pmax ~ Pmax |
Save Addr + 25 | KVA total | KVA/MVA | 0 ~ Pmax |
Save Addr + 26 | Sliding window maximum KW demand | KW/MW | 0 ~ Pmax |
Save Addr + 27 | Accumulated KW demand | ||
Save Addr + 28 ~ 30 | L1 ~ L3 Max. amp. demand | A | 0 ~ Imax |
Save Addr + 31 | Status inputs | Status value | |
Save Addr + 32 | KWh Export | KWh/MWh | 0 ~ -9999 |
Save Addr +33 | Sliding window maximum KVA demand | KVA/MVA | 0 ~ Pmax |
Save Addr + 34 ~ 36 | L1~L3/L12 ~ L31 THD Voltage | % | 0 ~ 999.9 |
Save Addr + 37 ~ 39 | L1~L3 THD Current | ||
Save Addr + 40 | KVAh | KVAh/MVAh | 0 ~ 99999999 |
Save Addr + 41 | Sliding window KW demand | KW/MW | -Pmax ~ Pmax |
Save Addr + 42 | Sliding window KVA demand | KVA/MVA | |
Save Addr + 43 | Reserved (Don't care) | - | - |
Save Addr + 44 ~ 46 | L1 ~ L3 TDD Current | % | 0 ~ 99.9 |
<Table 1> Memory save address and contents of DATA read (Only possible to read) |
Memory Save Address | Read/Write Address |
Contents | Unit | Range |
Save Addr + 0 | 0 | Wiring mode | - | 0 ~ 6, (0 = 3OP2, 1 = 4LN3, 2 = 3DIR2, 3 = 4LL3, 4 = 3OP3, 5 = 3LN3, 6 = 3LL3) |
1 | PT Ratio | 1.0 ~ 6500.0 |
||
2 | CT Primary Current | A | 1 ~ 50000 |
|
3 | Demand Interval | min | 1, 2, 5, 10, 15, 20, 30, 60, 255 = Outside Sync |
|
4 | Demand periods No | - | 1 ~ 15 |
|
5 | Ampere Demand Interval | sec | 0 ~ 1800 |
|
6 | Average Buf Size | - | 8, 16, 32 |
|
7 | Reset Enable/Disable | 0 = Disable, 1 = Enable |
||
8 | Basic Frequency | HZ | 50, 60 |
|
9 | Max Demand Load Current | A | 1 ~ 50000 |
|
10 | Phase Energy Mode | - | 0 = Disable, 1 = Enable |
|
<Table 2> Memory save address and contents of SETUP read/write (Only possible to read/write single Setup Data) |
Memory Save Address |
Contents |
Status by Bit |
Save Addr + 0 |
Relay Status |
0 ~ 5 Bit : Always 1, 6 Bit : Relay 2 Status, 7 Bit : Relay 1 Status, 8 ~ 15 Bit : Always 0,
* Relay Status 0 = Operated, 1 = Released |
<Table 3> Memory save address and contents of STATUS read (Only possible to read) |
Memory Save Address |
Contents |
Range |
Save Addr + 0 |
Firmware version Number |
0 ~ 65535 |
<Table 4> Memory save address and contents of VER read (Only possible to read) |
Memory Save Address | Read Address |
Contents |
Range |
Save Addr + 0 | AO Read = 0 ~ 15, ACH Read = 0 ~ 13 |
AO, ACH Read Register Number |
AO : 0 ~ 15, ACH : 0 ~ 13 |
Save Addr + 2 | AO, ACH allocation register parameter ID |
0 ~ 1611h (Refer to <Table 6>) |
|
Save Addr + 3 | AO, ACH zero scale (0/4 mA) |
Refer to <Table 6> |
|
Save Addr + 4 | AO ACH full scale (20/1 mA) |
||
<Table 5> Memory save address and contents of AO, ACH read (Only possible to read) |
ID Number(Hexadecimal) |
ID Number(Decimal) |
Contents |
Range |
Unit |
0h |
0 |
None |
0 |
- |
C00h ~ C03h |
3072 ~ 3074 |
Current value of the L1/L12 ~ L3/L31 voltage |
0 ~ Vmax |
V |
C03h ~ C05h |
3075 ~ 3077 |
Current value of the L1 ~ L3 current |
0 ~ Imax |
A |
F00h |
3840 |
Total KW Current Value |
-Pmax ~ Pmax |
KW |
F01h |
3841 |
Total Kvar Current Value |
Kvar | |
F02h |
3842 |
Total KVA Current Value |
0 ~ Pmax |
KVA |
F03h |
3843 |
Total PF Current Value |
-1 ~ 1 |
- |
F04h |
3844 |
Total PF lag Current Value |
0 ~ 1 |
|
F05h |
3845 |
Total PF lead Current Value |
||
1002h |
4098 |
Frequency |
0 ~ 100.0 |
HZ |
1100h ~ 1102h |
4352 ~ 5354 |
L1/L12 ~ L3/L31 average voltage |
0 ~ Vmax |
V |
1103h ~ 1105h |
4355 ~ 4357 |
L1 ~ L3 average current |
0 ~ Imax |
A |
1400h |
5120 |
Total KW average value |
-Pmax ~ Pmax |
KW |
1401h |
5121 |
Total Kvar average value |
Kvar | |
1402h |
5122 |
Total KVA average value |
0 ~ Pmax |
KVA |
1403h |
5123 |
Total PF average value |
-1 ~ 1 |
- |
1404h |
5124 |
Total PF lag average value |
0 ~ 1 |
|
1405h |
5125 |
Total PF lead average value |
||
1501h |
5377 |
Neutral average current |
0 ~ Imax |
A |
1502h |
5378 |
Average frequency |
0 ~ 100.0 |
HZ |
160Fh |
5647 |
Accumulated KW demand |
0 ~ Pmax |
KW |
1611h |
5649 |
Accumulated KVA demand |
KVA | |
<Table 6> Analog Output Parameter ID number and contents |
Memory Save Address | Read/Write Address | Contents |
Contents by Bit |
Save Addr + 0 | 0 | Status Input allocation |
0 ~ 3 bit = DI 1 ~ 4 allocation status, (0 : not allocated, 1 : allocated to the group)
4 ~ 15 bit = Don't care (0) |
1 | Pulse Input allocation |
||
2 | AO multiplexer allocation |
||
3 | External synchronization allocation |
||
<Table 7> Memory save address and contents of DI read/write |
Memory Save Address, Output Address |
Contents | Range |
Register ID No (Direct Address as Hexadecimal) |
Save Addr + 0 ~ 1 | No.1, No.2 Relay Control Status | 0 = Normal Operation, 1 = Force Operate, 2 = Force Release. |
8400h (No.1 Relay), 8401h (No.2 Relay) |
<Table 8> Memory save address and contents of RELAY read/write |
Memory Save Address |
Contents |
Range |
Save Addr + 0 |
Pulsing relay ID |
0 ~ 1 = No.1 ~ No.2 relay number |
Save Addr + 1 |
Pulsing setpoint Parameter ID of Designated Relay |
0 ~ 7 (0 = none, 1 = KWh import, 2 = KWh export, 4 = Kvarh import(inductive), 5 = Kvarh export(capacitive), 6 = Kvarh total, 7 = KVA total) |
Save Addr + 2 |
The number of Pulse per Pulsing setpoint unit time of designated relay |
Energy pulsing = 1 ~ 9999 Etc = 0. |
<Table 9> Memory save address and contents of PULSE read (Read) |
Output Parameter | Contents |
Range |
Station | ID number of RPT091 |
1 ~ 247 |
Address | Pulsing setpoint relay number |
0 or 1 (No.1 ~ No.2 relay number) |
Extra1 | PULSE |
Fixed (Command designation of PULSE write) |
Extra2 | Pulsing setpoint Parameter ID |
0 ~ 7 (Refer to <Table 9>) |
Output Value | - |
Energy pulsing = 1 ~ 9999 Etc = 0. |
<Table 10> Output parameter of PULSE write |
Memory Save Address |
Contents |
Range |
Save Addr + 0 |
Current time Sec (sec) |
0 ~ 59 |
Save Addr + 1 |
Current time Min (min) |
0 ~ 59 |
Save Addr + 2 |
Current time Hour (hour) |
0 ~ 23 |
Save Addr + 3 |
Current date Day (day) |
1 ~ 31 |
Save Addr + 4 |
Current date Month (month) |
1 ~ 12 |
Save Addr + 5 |
Current date Year (year) |
0 ~ 99 |
Save Addr + 6 |
Current date Week (day of the week) |
1 ~ 7 (1 = Sunday, ¡¦) |
<Table 11> Memory save address and contents of RTC read type |
*) RTC write command sends current time to Power Meter
Enter the output parameter to Extra1 as RTC, and set the remainder as blank(or 0).
Read Memory Save Address | Output Address | Contents |
Range (Hexadecimal) |
Register ID No (Direct Address as Hexadecimal) |
Save Addr + 0 ~ 119 | 0 ~ 119 | User-Define Register 0 ~ 119 |
0h ~ FFFFh (Register ID No) |
8100h ~ 8177h |
<Table 12> Memory save address and contents of DEFINE read/write |
Read Memory Save Address | Output Address | Contents |
Range |
Register ID No (Direct Address as Hexadecimal) |
Save Addr + 0 ~ 119 | 0 ~ 119 | User-Definable Data 0 ~ 119 |
According to Mapped(<Table 12>) Register ¡¦ |
8000h ~ 8077h |
<Table 13> Memory save address and contents of MAP read/write |
*) MAP write is only possible to output when the DEFINED Register ID number is 'Possible to Write Area'.
Memory Save Address | Read/Write Address | Contents | Range |
Register ID No (Direct Address as Hexadecimal) |
Save Addr + 0 | 0 | No.1 Alarm setpoint Trigger Parameter ID | 0 ~ 9405h (Refer to <Table 15>) |
8200h |
Save Addr + 1 | 1 | No.1 Alarm setpoint Action | 0 = No Action, 12288 = Operate Relay 1, 12289 = Operate Relay 2 |
8201h |
Save Addr + 2 ~ 3 | 2 ~ 3 | No.1 Alarm setpoint Operate, Release Delay | 0 ~ 9999 (x 0.1 Sec) |
8202h ~ 8203h |
Save Addr + 4 ~ 5 | 4 ~ 5 | No.1 Alarm setpoint Operate, Release limit | According to Parameter ID¡¦ (Refer to <Table 15>) |
8204h ~ 8205h |
Save Addr + 6 ~ 11 | 6 ~ 11 | No.2 Alarm setpoint ID, Action, Delay, Limit | Same with No.1 Alarm Setpoint |
8206h ~ 820Bh |
Save Addr + 12 ~ 89 | 12 ~ 89 | No.3 ~No.15 Alarm setpoint ID, Action, Delay, Limit | 820Ch ~ 8259h | |
Save Addr + 90 ~ 95 | 90 ~ 95 | No.16 Alarm setpoint ID, Action, Delay, Limit | 825Ah ~ 825Fh | |
<Table 14> Memory save address and contents of ALARM read/write |
Alarm Trigger Parameter ID(Hexadecimal) | Alarm Trigger Parameter ID(Decimal) | Contents |
Range | Unit |
0 | 0 | Don't care |
- | - |
600h ~ 603h | 1536 ~ 1539 | Status Input 1 ~ 4 ON |
||
8600h ~ 8603h | 34304 ~ 34307 | Status Input 1 ~ 4 OFF |
||
8901h | 35073 | Positive phase rotation Reversal |
||
8902h | 35074 | Negative phase rotation Reversal |
||
C03h ~ C05h | 3075 ~ 3077 | High current L1 ~ L3 |
0 ~ Imax | A |
8C03h ~ 8C05h | 35843 ~ 35845 | Low current L1 ~ L3 |
||
E00h | 3584 | High voltage current value |
0 ~ Vmax | V |
8D00h | 36096 | Low voltage current value |
||
E07h ~ E08h | 3591 ~ 3592 | High voltage/current THD |
0 ~ 999.9 | % |
E0Ah | 3594 | High current TDD |
0 ~ 100.0 | |
1002h | 4098 | High frequency |
0 ~ 100.0 | HZ |
9002h | 36866 | Low frequency |
||
1103h ~ 1105h | 4355 ~ 4357 | High current L1 ~ L3 average value |
0 ~ Imax | A |
9103h ~ 9105h | 37123 ~ 37125 | Low current L1 ~ L3 average value |
||
1300h | 4864 | High voltage average value |
0 ~ Vmax | V |
9200h | 37376 | Low voltage average value |
||
1406h ~ 1407h | 5126 ~ 5127 | High total KW import, export |
0~ Pmax | KW |
1408h ~ 1409h | 5128 ~ 5129 | High total Kvar import, export |
Kvar | |
1402h | 5122 | High total KVA |
KVA | |
9404h ~ 9405h | 37892 ~ 37893 | Low total PF lag, lead |
0 ~ 1.000 | - |
1501h | 5377 | High Neutral current |
0 ~ Imax | A |
1603h ~ 1605h | 5635 ~ 5637 | High ampere demand L1 ~ L3 |
||
1606h | 5638 | High block KW demand |
0 ~ Pmax | KW |
1608h | 5640 | High block KVA demand |
KVA | |
1609h | 5641 | High sliding window KW demand |
KW | |
160Bh | 5643 | High sliding window KVA demand |
KVA | |
160Fh | 5647 | High accumulated KW demand |
KW | |
1611h | 5649 | High accumulated KVA demand |
KVA | |
<Table 15> Trigger Parameter ID and contents of ALARM read/write command |
Memory Save Address | Read/Write Address | Contents | Range |
Register ID No (Direct Address as Hexadecimal) |
Write |
Save Addr + 0 | 0 | Reserved | Always 65535 |
8500h | - |
Save Addr + 1 | 1 | Interface | 1 = RS422, 2 = RS485 |
8501h | Possible |
Save Addr + 2 | 2 | Address | 0 ~ 247 |
8502h | |
Save Addr + 3 | 3 | Baud rate | 0 = 110, 1 = 300, 2 = 600, 3 = 1200, 4 = 2400, 5 = 4800, 6 = 9600, 7 = 19200 |
8503h | |
Save Addr + 4 | 4 | Data format | 0 = 7 data bits/even parity, 1 = 8 data bits/no parity, 2 = 8 data bits/even parity |
8504h | |
<Table 16> Memory save address and contents of COMM read/write |
Memory Save Address | Contents | Range |
Register ID No (Direct Address as Hexadecimal) |
Save Addr + 0 | Relay status | 0 ~ 1bit = No.1 ~ No.2 Relay status, (OFF : released, ON : Operate) 2bit ~ 15 bit = Don't care.(Always 0) |
7D00h |
Save Addr + 1 | Reserved | Always 0 |
7D01h |
Save Addr + 2 | Status inputs | 0 ~ 3bit = No.1 ~ No.4 Status input, (OFF : Open, ON : Closed) 4bit ~ 15 bit = Don't care.(Always 0) |
7D02h |
Save Addr + 3 | Setpoints status | 0 ~ 15bit = No.1 ~ No.16 Setpoints status, (OFF : released, ON : Operate) |
7D03h |
<Table 17> Memory save address and contents of ESR read (Only possible to read) |
Memory Save Address | Read/Write Address | Contents |
Range |
Register ID No (Direct Address as Hexadecimal) |
Save Addr + 0 | 0 | Setpoints alarm status |
0 ~ 15bit = No.1 ~ No.16 Setpoints alarm status (OFF : released, ON : Operate) |
7E00h |
Save Addr + 1 | 1 | Self-check alarm status |
0 bit = Reserved, 1 bit = ROM error, 2 bit = RAM error, 3 bit = Watchdog timer reset, 4 bit = Sampling failure, 5 bit = Out of control trap, 6 bit = Reserved, 7 bit = Timing failure, 8 bit = Loss of power (power up), 9 bit = External reset (warm restart), 10bit = Configuration corrupted, 11bit = RTC time synchronization required, 12 ~ 15 bit = reserved (OFF : released, ON : Operate) |
7E01h |
<Table 18> Memory save address and contents of ASR read/write |
Memory Save Address | Read/Write Address | Contents | Range |
Register ID No
(Direct Address as Hexadecimal)
|
Save Addr + 0 | 0 | Instrument Option 1 | 0 Bit : 120V Option, 1 Bit : 690V Option, 2 ~ 4 Bit : Reserved, 5 Bit : 50% current over range option, 6 Bit : Analog Output 0/4 ~ 20mA Option, 7 Bit : Analog Output 0 ~ 1mA Option, 8 Bit : Analog Output -1 ~ +1mA Option, 9 Bit : Relays Option, 10 Bit : Digital Inputs Option, 11 ~ 15 Bit : Reserved |
7F00h |
Save Addr + 1 | 1 | Instrument Option 2 | 0 ~ 2 Bit : Number of Relays - 1, 3 ~ 6 Bit : Number of Digital Inputs - 1, 7 ~ 15 Bit : Reserved, |
7F01h |
<Table 19> Memory save address and contents of OPTION read/write |
* DIRECT – Long Size Direct Read/Write, VARIABLE – Variable Size Direct Read/Write executes Read/Write by entering above <Table 1> ~ <Table 19> Register ID No (Direct address = Hexadecimal) address.
Read for DIRECT type to read always saves the 4 BYTE (8 BYTE ASCII data) data to Communication Program(PLC_SCAN.EXE) memory, and VARIABLE Read saves all read data to Communication Program(PLC_SCAN.EXE) memory as 1BYTE unit.
Also, Write sends the 1 BYTE( 2 BYTE ASCII data), 2 BYTE(4 BYTE ASCII data) and 4 BYTE(8 BYTE ASCII data) data to Power Meter, according to output type.