SATEC RPT091 ASCII Protocol's Save Contents and Output Address by Read/Write Type

 

In case of selecting SATEC RPT091 driver's communication protocol as ASCII(Open PROT terminal), save contents and address by read/write type are as follows.

Memory Save Address Contents Unit Range
Save Addr + 0 ~ 2 L1~L3/L12 ~ L31 Voltage V/KV 0 ~ Vmax
Save Addr + 3 ~ 5 L1 ~ L3 Current A 0 ~ Imax
Save Addr + 6 ~ 8 L1 ~ L3 Watt(KW) KW/MW -Pmax ~ Pmax
Save Addr + 9 ~ 11 L1 ~ L3 Power Factor - -0.99 ~ 1
Save Addr + 12 KW Total KW/MW -Pmax ~ Pmax
Save Addr + 13 Power Factor Total - -0.99 ~ 1
Save Addr + 14 KWh Import KWh/MWh 0 ~ 99999
Save Addr + 15 Neutral (Unbalanced) Current A 0 ~ Imax
Save Addr +16 Frequency HZ 45 ~ 65
Save Addr + 17 ~ 19 L1 ~ L3 Kvar Kvar/Mvar -Pmax ~ Pmax
Save Addr + 20 ~ 22 L1 ~ L3 KVA KVA/MVA -Pmax ~ Pmax
Save Addr + 23 Kvarh net Kvarh/Mvarh -9999.9 ~ 99999
Save Addr + 24 Kvar total Kvar/Mvar -Pmax ~ Pmax
Save Addr + 25 KVA total KVA/MVA 0 ~ Pmax
Save Addr + 26 Sliding window maximum KW demand KW/MW 0 ~ Pmax
Save Addr + 27 Accumulated KW demand
Save Addr + 28 ~ 30 L1 ~ L3 Max. amp. demand A 0 ~ Imax
Save Addr + 31 Status inputs   Status value
Save Addr + 32 KWh Export KWh/MWh 0 ~ -9999
Save Addr +33 Sliding window maximum KVA demand KVA/MVA 0 ~ Pmax
Save Addr + 34 ~ 36 L1~L3/L12 ~ L31 THD Voltage % 0 ~ 999.9
Save Addr + 37 ~ 39 L1~L3 THD Current
Save Addr + 40 KVAh KVAh/MVAh 0 ~ 99999999
Save Addr + 41 Sliding window KW demand KW/MW -Pmax ~ Pmax
Save Addr + 42 Sliding window KVA demand KVA/MVA
Save Addr + 43 Reserved (Don't care) - -
Save Addr + 44 ~ 46 L1 ~ L3 TDD Current % 0 ~ 99.9

<Table 1> Memory save address and contents of DATA read (Only possible to read)

Memory Save Address Read/Write
Address
Contents Unit

Range

Save Addr + 0 0 Wiring mode -

0 ~ 6,

(0 = 3OP2,

1 = 4LN3,

2 = 3DIR2,

3 = 4LL3,

4 = 3OP3,

5 = 3LN3,

6 = 3LL3)

1 PT Ratio

1.0 ~ 6500.0

2 CT Primary Current A

1 ~ 50000

3 Demand Interval min

1, 2, 5, 10, 15, 20, 30, 60,

255 = Outside Sync

4 Demand periods No -

1 ~ 15

5 Ampere Demand Interval sec

0 ~ 1800

6 Average Buf Size -

8, 16, 32

7 Reset Enable/Disable

0 = Disable,

1 = Enable

8 Basic Frequency HZ

50, 60

9 Max Demand Load Current A

1 ~ 50000

10 Phase Energy Mode -

 0 = Disable,

1 = Enable

<Table 2> Memory save address and contents of SETUP read/write (Only possible to read/write single Setup Data)

Memory Save Address

Contents

Status by Bit

Save Addr + 0

Relay Status

0 ~ 5  Bit : Always 1,

6      Bit : Relay 2 Status,

7      Bit : Relay 1 Status,

8 ~ 15 Bit : Always 0,

 

* Relay Status

0 = Operated,

1 = Released

<Table 3> Memory save address and contents of STATUS read (Only possible to read)

Memory Save Address

Contents

Range

Save Addr + 0

Firmware version Number

0 ~ 65535

<Table 4> Memory save address and contents of VER read (Only possible to read)
Memory Save Address

Read Address

Contents

Range

Save Addr + 0

AO Read = 0 ~ 15,

ACH Read = 0 ~ 13

AO, ACH Read Register Number

AO : 0 ~ 15,

ACH : 0 ~ 13

Save Addr + 2

AO, ACH allocation register parameter ID

0 ~ 1611h

(Refer to <Table 6>)

Save Addr + 3

AO, ACH zero scale (0/4 mA)

Refer to <Table 6>

Save Addr + 4

AO ACH full scale (20/1 mA)

<Table 5> Memory save address and contents of AO, ACH read (Only possible to read)

ID Number(Hexadecimal)

ID Number(Decimal)

Contents

Range

Unit

0h

0

None

0

-

C00h ~ C03h

3072 ~ 3074

Current value of the L1/L12 ~ L3/L31 voltage

0 ~ Vmax

V

C03h ~ C05h

3075 ~ 3077

Current value of the L1 ~ L3 current

0 ~ Imax

A

F00h

3840

Total KW Current Value

-Pmax ~ Pmax

KW

F01h

3841

Total Kvar Current Value

Kvar

F02h

3842

Total KVA Current Value

0 ~ Pmax

KVA

F03h

3843

Total PF Current Value

-1 ~ 1

-

F04h

3844

Total PF lag Current Value

0 ~ 1

F05h

3845

Total PF lead Current Value

1002h

4098

Frequency

0 ~ 100.0

HZ

1100h ~ 1102h

4352 ~ 5354

L1/L12 ~ L3/L31 average voltage

0 ~ Vmax

V

1103h ~ 1105h

4355 ~ 4357

L1 ~ L3 average current

0 ~ Imax

A

1400h

5120

Total KW average value

-Pmax ~ Pmax

KW

1401h

5121

Total Kvar average value

Kvar

1402h

5122

Total KVA average value

0 ~ Pmax

KVA

1403h

5123

Total PF average value

-1 ~ 1

-

1404h

5124

Total PF lag average value

0 ~ 1

1405h

5125

Total PF lead average value

1501h

5377

Neutral average current

0 ~ Imax

A

1502h

5378

Average frequency

0 ~ 100.0

HZ

160Fh

5647

Accumulated KW demand

0 ~ Pmax

KW

1611h

5649

Accumulated KVA demand

KVA
<Table 6> Analog Output Parameter ID number and contents
Memory Save Address Read/Write Address

Contents

Contents by Bit

Save Addr + 0 0

Status Input allocation

0 ~ 3 bit = DI 1 ~ 4 allocation status,

(0 : not allocated, 1 : allocated to the group)

 

4 ~ 15 bit = Don't care (0)

1

Pulse Input allocation

2

AO multiplexer allocation

3

External synchronization allocation

<Table 7> Memory save address and contents of DI read/write
Memory Save Address,
Output Address
Contents

Range

Register ID No

(Direct Address as Hexadecimal)

Save Addr + 0 ~ 1 No.1, No.2 Relay Control Status

0 = Normal Operation,

1 = Force Operate,

2 = Force Release.

 8400h (No.1 Relay),

8401h (No.2 Relay)

<Table 8> Memory save address and contents of RELAY read/write

Memory Save Address

Contents

Range

Save Addr + 0

Pulsing relay ID

0 ~ 1 = No.1 ~ No.2 relay number

Save Addr + 1

Pulsing setpoint Parameter ID of Designated Relay

0 ~ 7

(0 = none,

1 = KWh import,

2 = KWh export,

4 = Kvarh import(inductive),

5 = Kvarh export(capacitive),

6 = Kvarh total,

7 = KVA total)

Save Addr + 2

 The number of Pulse per Pulsing setpoint unit time of designated relay

Energy pulsing  = 1 ~ 9999

Etc = 0.

<Table 9> Memory save address and contents of PULSE read (Read)
Output Parameter

Contents

Range

Station

ID number of RPT091

1 ~ 247

Address

Pulsing setpoint relay number

0 or 1   (No.1  ~ No.2 relay number)

Extra1

PULSE

Fixed (Command designation of PULSE write)

Extra2

Pulsing setpoint Parameter ID

0 ~ 7  (Refer to <Table 9>)

Output Value

-

Energy pulsing  = 1 ~ 9999

Etc = 0.

<Table 10> Output parameter of PULSE write

Memory Save Address

Contents

Range

Save Addr + 0

Current time Sec (sec)

0 ~ 59

Save Addr + 1

Current time Min (min)

0 ~ 59

Save Addr + 2

Current time Hour (hour)

0 ~ 23

Save Addr + 3

Current date Day (day)

1 ~ 31

Save Addr + 4

Current date Month (month)

1 ~ 12

Save Addr + 5

Current date Year (year)

0 ~ 99

Save Addr + 6

Current date Week (day of the week)

1 ~ 7 (1 = Sunday, ¡¦)
<Table 11> Memory save address and contents of RTC read type

*) RTC write command sends current time to Power Meter

Enter the output parameter to Extra1 as RTC, and set the remainder as blank(or 0).

Read Memory Save Address Output Address

Contents

Range (Hexadecimal)

Register ID No

(Direct Address as Hexadecimal)
Save Addr + 0 ~ 119 0 ~ 119

User-Define

Register 0 ~ 119

0h ~ FFFFh

(Register ID No)

8100h ~ 8177h

<Table 12> Memory save address and contents of DEFINE read/write
Read Memory Save Address Output Address

Contents

Range

Register ID No

(Direct Address as Hexadecimal)
Save Addr + 0 ~ 119 0 ~ 119

User-Definable

Data 0 ~ 119

According to Mapped(<Table 12>) Register ¡¦

8000h ~ 8077h

<Table 13> Memory save address and contents of MAP read/write

*) MAP write is only possible to output when the DEFINED Register ID number is 'Possible to Write Area'.

Memory Save Address Read/Write Address Contents

Range

Register ID No
(Direct Address as Hexadecimal)
Save Addr + 0 0 No.1 Alarm setpoint Trigger Parameter ID

0 ~ 9405h

(Refer to <Table 15>)

8200h
Save Addr + 1 1 No.1 Alarm setpoint Action

0 = No Action,

12288 = Operate Relay 1,

12289 = Operate Relay 2

8201h
Save Addr + 2 ~ 3 2 ~ 3 No.1 Alarm setpoint Operate, Release Delay

0 ~ 9999 (x 0.1 Sec)

8202h ~ 8203h
Save Addr + 4 ~ 5 4 ~ 5 No.1 Alarm setpoint Operate, Release limit

According to Parameter ID¡¦

(Refer to <Table 15>)

8204h ~ 8205h
Save Addr + 6 ~ 11 6 ~ 11 No.2 Alarm setpoint ID, Action, Delay, Limit

Same with No.1 Alarm Setpoint

8206h ~ 820Bh
Save Addr + 12 ~ 89 12 ~ 89 No.3 ~No.15 Alarm setpoint ID, Action, Delay, Limit 820Ch ~ 8259h
Save Addr + 90 ~ 95 90 ~ 95 No.16 Alarm setpoint ID, Action, Delay, Limit 825Ah ~ 825Fh
<Table 14> Memory save address and contents of ALARM read/write
Alarm Trigger Parameter ID(Hexadecimal) Alarm Trigger Parameter ID(Decimal)

Contents

Range Unit
0 0

Don't care

- -
600h ~ 603h 1536 ~ 1539

Status Input 1 ~ 4 ON

8600h ~ 8603h 34304 ~ 34307

Status Input 1 ~ 4 OFF

8901h 35073

Positive phase rotation Reversal

8902h 35074

Negative phase rotation Reversal

C03h ~ C05h 3075 ~ 3077

High current L1 ~ L3

0 ~ Imax A
8C03h ~ 8C05h 35843 ~ 35845

Low current L1 ~ L3

E00h 3584

High voltage current value

0 ~ Vmax V
8D00h 36096

Low voltage current value

E07h ~ E08h 3591 ~ 3592

High voltage/current THD

0 ~ 999.9 %
E0Ah 3594

High  current TDD

0 ~ 100.0
1002h 4098

High frequency

0 ~ 100.0 HZ
9002h 36866

Low frequency

1103h ~ 1105h 4355 ~ 4357

High current L1 ~ L3 average value

0 ~ Imax A
9103h ~ 9105h 37123 ~ 37125

Low current L1 ~ L3 average value

1300h 4864

High voltage average value

0 ~ Vmax V
9200h 37376

Low voltage average value

1406h ~ 1407h 5126 ~ 5127

High total KW import, export

0~ Pmax KW
1408h ~ 1409h 5128 ~ 5129

High total Kvar import, export

Kvar
1402h 5122

High total KVA

KVA
9404h ~ 9405h 37892 ~ 37893

Low total PF lag, lead

0 ~ 1.000 -
1501h 5377

High Neutral current

0 ~ Imax A
1603h ~ 1605h 5635 ~ 5637

High ampere demand L1 ~ L3

1606h 5638

High block KW demand

0 ~ Pmax KW
1608h 5640

High block KVA demand

KVA
1609h 5641

High sliding window KW demand

KW
160Bh 5643

High sliding window KVA demand

KVA
160Fh 5647

High accumulated KW demand

KW
1611h 5649

High accumulated KVA demand

KVA
<Table 15> Trigger Parameter ID and contents of ALARM read/write command
Memory Save Address Read/Write Address Contents

Range

Register ID No
(Direct Address as Hexadecimal)
Write
Save Addr + 0 0 Reserved

Always 65535

8500h -
Save Addr + 1 1 Interface

1 = RS422,

2 = RS485

8501h Possible
Save Addr + 2 2 Address

0 ~ 247

8502h
Save Addr + 3 3 Baud rate

0 = 110,

1 = 300,

2 = 600,

3 = 1200,

4 = 2400,

5 = 4800,

6 = 9600,

7 = 19200

8503h
Save Addr + 4 4 Data format

0 = 7 data bits/even parity,

1 = 8 data bits/no parity,

2 = 8 data bits/even parity

8504h
<Table 16> Memory save address and contents of COMM read/write
Memory Save Address Contents

Range

Register ID No
(Direct Address as Hexadecimal)
Save Addr + 0 Relay status

0 ~ 1bit = No.1 ~ No.2 Relay status,

    (OFF : released, ON : Operate)

2bit ~ 15 bit = Don't care.(Always 0)

7D00h
Save Addr + 1 Reserved

Always 0

7D01h
Save Addr + 2 Status inputs

0 ~ 3bit = No.1 ~ No.4 Status input,

    (OFF : Open, ON : Closed)

4bit ~ 15 bit = Don't care.(Always 0)

7D02h
Save Addr + 3 Setpoints status

0 ~ 15bit = No.1 ~ No.16 Setpoints status,

(OFF : released, ON : Operate)

7D03h
<Table 17> Memory save address and contents of ESR read (Only possible to read)
Memory Save Address Read/Write Address

Contents

Range

Register ID No

(Direct Address as Hexadecimal)
Save Addr + 0 0

Setpoints alarm status

0 ~ 15bit = No.1 ~ No.16 Setpoints alarm status

(OFF : released, ON : Operate)

7E00h

Save Addr + 1 1

Self-check alarm status

0 bit = Reserved,

1 bit = ROM error,

2 bit = RAM error,

3 bit = Watchdog timer reset,

4 bit = Sampling failure,

5 bit = Out of control trap,

6 bit = Reserved,

7 bit = Timing failure,

8 bit = Loss of power (power up),

9 bit = External reset (warm restart),

10bit = Configuration corrupted,

11bit = RTC time synchronization required,

12 ~ 15 bit = reserved

(OFF : released, ON : Operate)

7E01h

<Table 18> Memory save address and contents of ASR read/write
Memory Save Address Read/Write Address Contents

Range

Register ID No

(Direct Address as Hexadecimal)
Save Addr + 0 0 Instrument Option 1

0  Bit : 120V Option,

1  Bit : 690V Option,

2 ~ 4  Bit : Reserved,

5  Bit : 50% current over range option,

6  Bit : Analog Output 0/4 ~ 20mA Option,

7  Bit : Analog Output 0 ~ 1mA Option,

8  Bit : Analog Output -1 ~ +1mA Option,

9  Bit : Relays Option,

10 Bit : Digital Inputs Option,

11 ~ 15 Bit : Reserved

7F00h

Save Addr + 1 1 Instrument Option 2

0 ~ 2 Bit : Number of Relays - 1,

3 ~ 6 Bit : Number of Digital Inputs - 1,

7 ~ 15  Bit : Reserved,

7F01h

<Table 19> Memory save address and contents of OPTION read/write

* DIRECT – Long Size Direct Read/Write, VARIABLE – Variable Size Direct Read/Write executes Read/Write by entering above <Table 1> ~ <Table 19> Register ID No (Direct address = Hexadecimal) address.

Read for DIRECT type to read always saves the 4 BYTE (8 BYTE ASCII data) data to Communication Program(PLC_SCAN.EXE) memory, and VARIABLE Read saves all read data to Communication Program(PLC_SCAN.EXE) memory as 1BYTE unit.

Also, Write sends the 1 BYTE( 2 BYTE ASCII data), 2 BYTE(4 BYTE ASCII data) and 4 BYTE(8 BYTE ASCII data) data to Power Meter, according to output type.