RKC CB100-CB900 communication driver is the driver to communicate with CB100, CB400, CB500, CB700 and CB900 module digital controller of RKC Instrument Corp., in Japan.
<Figure 1> is read setting example of RKC CB100-CB900 driver.
<Figure 1> Read setting example of RKC CB100-CB900 driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively according to setting of controller.
RKC CB100-CB900 driver's read schedule
Read schedule setting parameters are as follows :
1) STATION – STATION number set at controller(0~99).
2) Read Type – Input memory type. Refer to <Table 1>.
3) Read start address – Don't care.
4) Save Start Address for Communication Server – readed data saving start address of communication server.
5) Read Size – Fixed to 1.
Read schedule example)
READ | STATION | Read Type | Read Start Address | Memory Save Address | Read Size(Fixed to 1) |
FLOAT, | 1, | M1, | 0, | 0, | 1, |
FLOAT, | 1, | S1, | 0, | 1, | 1, |
<Table 1> is memory area possible to be used at RKC CB100-CB900 protocol.
Area | Data Type |
Remarks |
M1 | Measured Value : PV |
Read only. |
M2, M3 | transformer input1, 2 |
0.0 ~ 100.0A, Read only. |
AA, AB | Alarm 1, 2 Status |
0:OFF, 1:ON, Read only. |
B1 | Burnout |
0:OFF, 1:ON, Read only. |
ER | Error Code |
0 ~ 255, Read only. |
SR | RUN/STOP Function |
0:OFF, 1:ON, Read/Write. |
S1 | Set value(SV) |
SV Setting Value, Read/Write. |
A1, A2 | Alarm 1, 2 Setting |
Read/Write. |
A3, A4 | Heat break alarm 1, 2 Setting |
0.0 ~ 100.0A, Read/Write. |
A5 | Control loop break alarm Setting |
0.1 ~ 200.0 min, Read/Write. |
A6 | LBA deadband Setting |
Temp:0~9999, Voltage-current:0~100%, Read/Write. |
G1 | Autotuning |
0:STOP, 1:RUN, Read/Write. |
G2 | Self-tuning |
0:STOP, 1:RUN, Read/Write. |
P1 | Heat-side proportional band |
Read/Write. |
I1 | Integral time |
1~3600 sec(0:PD control), Read/Write. |
D1 | Derivative time |
1~3600 sec(0:PI control), Read/Write. |
W1 | Anti-reset windup |
1~100%(0:integral action OFF), Read/Write. |
T0 | Heat-side proportioning cycle |
1~100 sec, Read/Write. |
P2 | Cool-side proportioning band |
1~1000% sec, Read/Write. |
V1 | Deadband |
Temp Input :-10~10, Read/Write. |
T1 | Cool-side proportioning cycle |
1~100 sec, Read/Write. |
PB | PV Voltage |
-1999~1999 or -199.9~199.9, Read/Write.. |
LK | Set data lock Function |
0~7, Read/Write. |
<Table 1> Memory area possible to be used at RKC CB100-CB900 protocol |
Write to direct address of controller, regardless of SCAN File.
Digital Write
Digital write setting parameters are as follows :
1) PORT Connected PORT number
2) Station Station number 0 ~ 99.
3) ADDRESS Don't care
4) Extra1 Memory area Refer to <Table 1>
5) Extra2 Don't care
Write example 1)
Station:1, Extra1:SR
The setting parameter shown above is example for RUN/STOP the RKC controller.
Analog Write
Analog write setting parameters are as follows :
1) PORT Connected PORT number
2) Station Station number 0 ~ 99.
3) ADDRESS Don't care
4) Extra1 Memory area Refer to <Table 1>
5) Extra2 Entire the number of digits, Integer : 1, Etc : 0 or the number of digits
Write example 1)
STATION:1, EXTRA1:S1
The setting parameter shown above is setting SV value(set value) example for RKC controller.