PM-B communication driver is the driver to communicate with PM series power meter controller of Light Star Instrument Co., Ltd. in Korea.
PM-B communicaton compatible with the controller PM-? series and Analog Signal Input( KCAI )/Digital Signal Input Module ( KCDI ) module.
<Figure 1> is read Schedule setting example of PM-B communication driver.
<Figure 1> Read Schedule setting example of PM-B communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively according to setting of controller.
PM-B communication driver¡¯s read schedule
Read schedule setting parameters are as follows:
1) STATION – station number of PM-B controller.
2) Read memory type – memory = D( analog ), X ( digital ). (refer to <Table 1> ~ <Table 2> )
3) Read start address – start reading address in memory.
4) Save Start Address for Communication Server – Input save start address of communication server.
5) Read Size – word unit read size.
Read schedule example)
READ, 1, D, 0, 0, 14,
READ, 1, X, 0, 20, 1,
<Table 1>, <Table 2> are address and contents of D and X memory type.
Address(word unit) | Contents |
D0000 | volatge (V1) |
D0001 | volatge (V2) |
D0002 | volatge (V3) |
D0003 | current (A1) |
D0004 | current (A2) |
D0005 | current (A3) |
D0006 | power (W) |
D0007 | power factor(PF) |
D0008 | reactive power (VAR) |
D0009 | frequency(Hz) |
D000A | amount of power (WH higher) |
D000B | amount of power(WH lower) |
D000C | amount of reactive power(VARH higher) |
D000D | amount of reactive power(VARH lower) |
<Table 1> Address and contents of D memory type |
Address(word unit) | Contents |
X0000 | Digital Input 1 |
X0001 | Digital Input 2 |
X0002 | Digital Input 3 |
X0003 | Digital Input 4 |
X0004 | Digital Input 5 |
X0005 | Digital Input 6 |
X0006 | Digital Input 7 |
X0007 | Digital Input 8 |
X0008 | Digital Input 9 |
X0009 | Digital Input 10 |
X000A | Digital Input 11 |
X000B | Digital Input 12 |
X000C | Digital Input 13 |
X000D | Digital Input 14 |
X000E | Digital Input 15 |
X000F | Digital Input 16 |
<Table 2> Address and contents of X memory type |
PM-B communication driver don't support 'write settings'.