PDMS-S Protocol Communication Driver

 

PDMS-S Protocol is the driver to communicate with Partial Discharge Monitoring System for SWGR controller of Woo Ri E&C in Korea.

 

1. Read settings

<Figure 1> is read setting example of PDMS-S Protocol communication driver.

<Figure 1> Read setting example of PDMS-S Protocol communication driver

 

Device part of  <Figure 1> input Device Type(TCP/IP), IP address of controller(192.168.0.9 ), service port for TCP(45000) respectively, accordint to the setting of controller.

 

Read schedule of PDMS-S Protocol communication driver

Read schedule setting parameters are as follows:

1) station – don't care. (fixed to 0)

2) read command – Command : DATA ( refer to <Table 1> ).

3) read start address – don't care.

4) Save start address for Communication Server – Saving start address of Communication Server.

5)    Read size – fixed to 1.

 

Read schedule example) 

READ, 0, DATA, 0, 0, 1,

 

<Table 1> is data saving address and value of PDMS-S Protocol communication driver.

Read command

Contetns

Data saving value of Communication Server 

Remarks

DATA

Read of current data

Saving Start Address + 0 : current data 1

Saving Start Address + 1 : current data 2

......

Saving Start Address + n : current data n

save each readed byte value to memory
<Table 1> Data saving address and value of PDMS-S Protocol communication driver

PDMS-S Protocol communication driver store the same data in WORD, DWORD, FLOAT, DOUBLE memory, but the data format are different.

If you click the icon  in protocol option part at <Figure 1>, you can see the dialog box such as <Figure 2>. you can also set read schedule by using this part. 

<Figure 2> Example of PDMS-S Protocol communication driver¡¯s Option dialog box

 

You can set read schedule by using , ,  button and listbox of <Figure 2>.

<Figure 3> Example of PDMS-S Protocol communication driver¡¯s read schedule Add/Edit dialog box

 

When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.

 

2. Write settings

You can set setting value  by using 'write settings'. 

 

Digital Write

Digital write and analog write have the same setting parameters except output value. 

 

Analog Write 

Analog write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             don't care.

3)  ADDRESS          0 ~ 100 THD setting value.

4)  Extra1                  write command : SET.

5)  Extra2                 0 ~ 31 input signal amplification value. ( default = 0)

6) Output value      1 ~ 99 event level. ( 50 =  alarm more than 50% )

 

Write example 1) 

PORT : 0   STATION : 0   ADDRESS : 0  EXTRA1 : SET  EXTRA2 : 0  

The setting parameter shown above is event level setting example.  ( setting value : 1 ~ 99 level )

 

3. Appearance of PDMS-S

<Figure 4> shows the appearance of PDMS-S controller.

<Figure 4> Appearance of PDMS-S controller