MASTER-K10/60/200 communication driver

 

MASTER-K 10/60/200 communication driver is the driver to communicate with MASTER-K 10/30/50/60/200 series PLC of LSIS Co., Ltd.  in Korea.

 

1. Read Settings

 

<Figure 1> is read setting example of MASTER-K 10/60/200 communication driver.

<Figure 1>  Read setting example of MASTER-K 10/60/200 communication driver

Device part of  <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively according to PLC.

Baud rate, parity bit, data bit, stop bit of MASTER-K 10/30/50/60/200 series are fixed to 9600, 0, 8, 1. ( K500/1000 model can set by using Dip switch )

 

MASTER-K 10/60/200 communication driver read schedule

Read schedule setting parameters are as follows:

1) Station – PLC station number. ( K500/1000 model )

2) Read memory type – memory type of PLC = (P(input/output), M, L, K, F, T, C, D, S, ...

3) Read start address – reading start address in PLC memory.

4) Save start address for Communication Server – Saving start address of Communication Server.

5) Read Size – word unit read size.

 

Read schedule example)

READ, 0, M, 0, 0, 2,
READ, 0, L, 0, 2, 2,
READ, 0, K, 0, 4, 2,
READ, 0, F, 0, 6, 2,

 

2. Writing settings

You can set MASTER-K 10/30/50/60/200 series PLC by using write settings.

 

Digital Write

Digital write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             PLC station number when  K500/1000 model.

3)  ADDRESS          write address in memory.

4)  Extra1                   write memory type = P,M,L,K.

5)  Extra2                   don't care.

 

Write example 1) 

PORT : 0  Station : 0, ADDRESS : 0100, EXTRA1 : M,  EXTRA2 : 0

The setting parameter shown above is a control(On/Off) example of M0100 address.

 

Analog Write

Analog write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             PLC station number when  K500/1000 model.

3)  ADDRESS          decimal unit write address in memory.

4)  Extra1                   write memory type = P,M,L,K,T,C,D,S.

5)  Extra2                   don't care.

 

Write example 1) 

PORT : 0  Station : 0, ADDRESS : 0090, EXTRA1 : L,  EXTRA2 : 0

The setting parameter shown above is word unit write setting example of L0090 address.

 

3. Pin assignment of 25 pin communication connector

Pin assignment of 25 pin communication connector is as follows.

 

1) MASTER-K30/50/60/200

when RS-232C communication

2 - TxD

3 - RxD

5 – GND

 

2) MASTER-K250/500/1000

when RS-232C communication

2 - TxD

3 – RxD

7 – GND

 

when RS-422 communication

10 – SD(+)

11 – SD(-)