K-TURBO Blower communication driver is the driver to communicate with blower controller.
<Figure 1> is read setting example of K-TURBO Blower communication driver.
<Figure 1> Read setting example of K-TURBO Blower communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(19200), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to controller.
K-TURBO Blower communication driver read schedule
Read schedule setting parameters are as follows:
1) Station – Don't care.
2) Read command – Don't care.
3) Read start address – Don't care.
4) Save start address for Communication Server – Saving start address of Communication Server.
5) Read Size – Fixed to 1.
Read schedule example)
READ, 0, 0, 0, 0, 1,
K-TURBO Blower communication driver save the readed data from controller.( refer to <Table 1> ) The controller send periodically data to communication driver.
<Table 1> is data saving address and contents for K-TURBO Blower communication driver.
Data saving address |
Contents |
Range |
Start addr + 0 |
pressure |
0 ~ 25599 ( real value = 0.00 ~ 255.99 ) |
Start addr + 1 |
pressure difference at filter |
|
Start addr + 2 |
operation pressure of setting BOV |
|
Start addr + 3 |
moter RPM |
0 ~ 40000 |
Start addr + 4 |
input motor current |
|
Start addr + 5 |
target mortor RPM |
0 ~ 40000 |
Start addr + 6 |
setting operation value |
|
Start addr + 7 |
run stauts 1 00h = preparing 01h = READY 02h = FAULT 04h = unload run status 08h = load run status |
eac bit status |
Start addr + 8 |
run status 2 01h = Max Flow Mode 02h = Set Flow Mode 03h = Feedback Mode 04h = TBD |
|
Start addr + 9 |
run status 3 01h = error of temperature sensor 02h = error of pressure sensor 04h = error of motor current 08h = error of motor rotation 10h = error of inverter 20h = over-heat status of inverter 40h = failure of start 80h = error of motor abnormal |
|
<Table 1> Data saving address and contents for K-TURBO Blower communication driver |
If you click the icon in protocol option part at <Figure 1>, you can see the help dialogue box such as <Figure 2>.
<Figure 2> Help dialog box of K-TURBO Blower communication driver |
You can control K-TURBO Blower controller by using 'writing settings'.
Digital Write
Digital write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION Don't care.
3) ADDRESS Don't care.
4) Extra1 Write command.
A : setting of operation mode,
B : setting of operation command,
C : setting of BOV operation pressure,
D : setting of operation.
5) Extra2 Selection of feedback mode, operation load when A, D write command.
0 : Set Flow Mode, unload operation,
1 : Feedback Mode, load operation.
Write example 1)
PORT:0, station:0, ADDRESS:0000, Extra1: A, Extra2 : 0, Output value = Off
The setting parameter shown above is a setting example to Max Flow mode.
Write example 2)
PORT:0, station:0, ADDRESS:0000, Extra1: A, Extra2 : 0, Output value = On
The setting parameter shown above is a setting example to Set Flow mode.
Write example 3)
PORT:0, station:0, ADDRESS:0000, Extra1: A, Extra2 : 1, Output value = On
The setting parameter shown above is a setting example to Feedback mode.
Write example 4)
PORT:0, station:0, ADDRESS:0000, Extra1: D, Extra2 : 0, Output value = Off
The setting parameter shown above is stop setting example of Unload operation.
Write example 5)
PORT:0, station:0, ADDRESS:0000, Extra1: D, Extra2 : 0, Output value = On
The setting parameter shown above is start setting example of Unload operation.
Write example 6)
PORT:0, station:0, ADDRESS:0000, Extra1: D, Extra2 : 1, Output value = On
The setting parameter shown above is start setting example of Load operation.
Analog Write
Analog write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION Don't care.
3) ADDRESS Don't care.
4) Extra1 Write command.
A : setting of operation mode,
B : setting of operation command,
C : setting of BOV operation pressure,
D : setting of operation.
5) Extra2 Don't care.
Write example 1)
PORT:0, station:0, ADDRESS:0000, Extra1: B, Extra2 : 0
The setting parameter shown above is setting example of operation command( output value = 0 ~ 255 ).
Write example 2)
PORT:0, station:0, ADDRESS:0000, Extra1: C, Extra2 : 0
The setting parameter shown above is setting example of BOV operation pressure( output value = 0 ~ 25599, real setting value = 0.00 ~ 255.99 ).