KD Power AD-204 communication driver is the driver to communicate with AD-204 controller of KD Power Co,. Ltd. in Korea.
<Figure 1> is read setting example of KD Power AD-204 communication driver.
<Figure 1> Read setting example of KD Power AD-204 communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to controller.
In protocol option part, you can set the following: weather to portable controller of master equipment(0 : normal, 1 : portable, default = 0).
KD Power AD-204 communication driver read schedule
Read schedule setting parameters are as follows:
1) Station – 0 ~ 255 controller station number. portable controller = 1.
2) Read command – Command = A or space. ( refer to <Table 1> )
3) Read start address – Don't care.
4) Save start address for Communication Server – Saving start address of Communication Server.
5) Read Size – Fixed to 1.
Read schedule example)
READ, 1, A, 0, 0, 1,
<Table 1> is data saving address and contents of KD Power AD-204 communication driver.
Read command | Contents | Data saving address |
A | Read of current Data value | Start addr + 0 ~ 3 : AD channel value of 1 ~ 4 |
<Table 1> Data saving address and contents of KD Power AD-204 communication driver |
KD Power AD-204 communication driver store the same data in WORD, DWORD, FLOAT, STRING memory, but the data format are different.
If you click the icon in protocol option part at <Figure 1>, you can see the dialogue box such as <Figure 2>. you can also set read schedule by using this part.
<Figure 2> Example of KD Power AD-204 communication driver¡¯s Option dialog box |
You can set read schedule by using , , button and listbox of <Figure 2>.
Also, you can set weather to portable controller of master equipment by using the part of 'Master is PP' of <Figire 2>.
<Figure 3> Example of KD Power AD-204 communication driver¡¯s read schedule Add/Edit dialog box |
When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.
KD Power AD-204 communication driver don't support 'Writing settings'.
Connection of communication cable and main power are as follows.
Connection of communication cable
Please connect A1, B1(RS-485) connector of AD-204 and T+, T- of computer such as <Figure 4>.
<Figure 4> Connection example of communication cable and main power to AD-204 controller |
Connection of main power
Please connect 220V AC power to main power connector such as <Figure 4>.