KACO Pawador Inverter communication driver

 

KACO Pawador Inverter communication driver is the driver to communicate with inverter controller of KACO Geratetechnic GmbH in Germany.

 

1. Read Settings

 

<Figure 1> is read setting example of KACO Pawador Inverter communication driver.

<Figure 1>  Read setting example of KACO Pawador Inverter communication driver

Device part of  <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to controller.

 

KACO Pawador Inverter communication driver read schedule 

Read schedule setting parameters are as follows:

1) Station – 1 ~ 32 controller station number.

2) Read data type – 0 : 3000xi model = read of 3000xi identify, other model = read of inverter data,

1 ~ 3 : part 1 ~ 3 inverter data for 3000xi model.

3) Controller model –  0 : 3000xi model, 1 : 2500xi ~ 5000xi, 1501xi ~ 3501xi, etc.

4) Save start address for Communication Server – Saving start address of Communication Server.

5) Read Size – Fixed according to read data type.

 

Read schedule example)  

READ,     1,    0,     0,    0,  1,

READ,     2,    0,     0,   10,  1,

 

<Table 1> is data saving address and contents for KACO Pawador Inverter communication driver.

<Table 2> is data value and contents for status data.

Data saving address Contents Units Remarks
Start addr + 0 0 ~ 3 read data type -  
Start addr + 1 status data - refer to <Table 2>
Start addr + 2 generator voltage V  
Start addr + 3 generator current A  
Start addr + 4 generator power W  
Start addr + 5 grid voltage V  
Start addr + 6 grid current, delivered current A  
Start addr + 7 grid-feeding power W  
Start addr + 8 temperature of controller ¡É  
Start addr + 9 Yield Today Wh  
Start addr + 10 inverter type, mnemonic   save also at STRING memory
Start addr + 11 total Yield KWh  
<Table 1> Data saving address and contents for KACO Pawador Inverter communication driver

Status value

Contents

0

Inverter has just switched on

1

Waiting for start

2

Waiting for shut down

3

Constant voltage regulator

4

MPP-tracker, permanent search/tracking movement

5

MPP-tracker, without search/tracking movement

6

Wait mode before grid feeding, Test grid and solar voltage

7

Wait mode before self test, Test grid and solar voltage

8

Self-test relays

10

Over temperature shut-off

11

Power limitation

12

Overload shut-off

13

Over voltage shut-off

14

Grid failure(1 phase monitoring)

15

Transition to night shut-down

18

RCD shut-down

19

Insufficient insulation resistance

30

Measuring error

31

RCD module error

32

Self-test error

33

DC grid-feeding error

34

Communication error

<Table 2> Data value and contents for status data

KACO Pawador Inverter communication driver store the same data in WORD, DWORD, FLOAT memory, but the data format are different.

If you click the icon  in protocol option part at <Figure 1>, you can see the dialogue box such as <Figure 2>. you can also set read schedule by using this part. 

<Figure 2> Example of KACO Pawador Inverter communication driver¡¯s Option dialog box

You can set read schedule by using , , button and listbox of <Figure 2>.

<Figure 3> Example of KACO Pawador Inverter communication driver¡¯s read schedule Add/Edit dialog box

When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.

 

2. Writing settings

KACO Pawador Inverter communication driver don't support 'Writing settings'.

 

 

3. Apperance of KACO Pawador controller

<Figure 4> is apperance of KACO Pawador Inverter controller.

<Figure 4> Apperance of KACO Pawador Inverter controller