HYDRAN 201Ti communication driver

 

 

HYDRAN 201Ti communication driver is the driver to communicate with Intelligent Transmitter of General Electric Canada Inc. in Canada.

 

1. Read Settings

 

<Figure 1> is read setting example of HYDRAN 201Ti communication driver.

<Figure 1>  Read setting example of HYDRAN 201Ti communication driver

Device part of  <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to setting of controller.

 

Note) HYDRAN 201Ti controller can set baud rate between 2400, 4800, 9600, also parity bit, data bit, stop bit are fixed to 0, 8, 1.

 

HYDRAN 201Ti communication driver read schedule

Read schedule setting parameters are as follows:

1) Station – 0 ~ 254 controller station(address) number. 0 = Nobody Listens, 255 = Everybody listens(broadcast).

2) Read command – Command = 0 ~ 31. refer to <Table 1>.

3) Read Start Address Reading start address(decimal unit) according to 'read command'. refer to <Table 2>, <Table 3>.

4) Save start address for Communication Server – Saving start address of Communication Server.

5) Read Size – Fixed to 1.

 

Read schedule example)

FLOAT,     1,    6,     0,    0,   1,

FLOAT,     1,    6,     6,    1,   1,

FLOAT,     1,    6,     7,    2,   1,

FLOAT,     1,    6,     8,    3,   1,

FLOAT,     1,    6,     9,    4,   1,

FLOAT,     1,    6,    10,    5,   1,

FLOAT,     1,    6,    11,    6,   1,

FLOAT,     1,    6,    12,    7,   1,

 

<Table 1> is command number and contents of HYDRAN 201Ti communication driver.

<Table 2>, <Table 3> are data number and contents of System Variable(5, 6 command), System Boolean(7, 8 command).

 

Command number

Contents

Remarks

0

Null command

for connection test command

1 ~ 4

Command for General Electric Canada

 

5

Write of System Variable, refer to data number of <Table 2>

analog write

6

Read of System Variable, refer to data number of <Table 2>

read

7

Write of System Boolean

 digital wirite

8

Read of System Boolean

 

9 ~ 10

Command for General Electric Canada

 

11

Read of Histo Record

 

12

Next Histo Record

 

13

Previous Histo Record

 

14

Histo Start Date

 

15

Rewind Histo Files

 

16

Force Sensor Test

 

17

Alarm Recognized

 

18 ~ 19

Command for General Electric Canada

 

20

Status

 

21

Clear Histo

 

22

Command for General Electric Canada

 

23

Read of Date/Time

 

24

Write of Date/Time

 

25 ~ 26

Command for General Electric Canada

 

27

End of Transmits

 

28

New Sensor

 

29

System Status Asked from the Remote Host Computer

 

30

Clear One of the Four Histo

 

31

Command for General Electric Canada

 

<Table 1> Command number and contents of HYDRAN 201Ti communication driver

 

Data number

Contents

Min range

Max range

0

Gas ppm value

0

0

1 ~ 2

Hourly/Daily Trend

0

0

3

Sensor Temperature

0

0

4

Battery Voltage

0

0

5

Sensor Test Result

0

0

6 ~ 7

Gas Set-Point Low Low/Low

0

2000

8 ~ 9

Gas Set-Point High/High High

0

2000

10 ~ 11

Hourly Set-Point Low Low/Low

-99.9

99.9

12 ~ 13

Hourly Set-Point High/High High

-99.9

99.9

14 ~ 15

Daily Set-Point Low Low/Low

-2000

2000

16 ~ 17

Daily Set-Point High/High High

-2000

2000

18 ~ 19

Sensor Temperature Set-Point Low Low/Low

-40

90

20 ~ 21

Sensor Temperature Set-Point High/High High

-40

90

22

Battery Set-Point Low Low

1.7

3.0

23

Battery Set-Point Low

1.8

3.0

24

Battery Set-Point High

0

4

25

Set-up Lost(version 2.2)

-1

-7

30

Gas Alarm Delay

0

300

31 ~ 31

Hourly/Daily Trend Alarm Delay

0

300

35

Sensor Test Alarm Delay

0

300

36

Period B

0

250

37

Hourly Trend Period

0.1

99.9

38

Daily Trend Period

1

99

39

Histo Short-term Ramte(minute)

1

360

40

heating Plate Temperature( ¡É )

0

0

41

Service¥°

0

0

42

Service A

0

0

43

Heater Power

0

0

60

General Histo Year

1994

2094

61

General Histo Month

1

12

62

General Histo Day

1

31

63

General Histo Hour

0

23

64

General Histo Minute

0

59

67 ~ 68

Gas High/High High Relay Mode

0

3

69

System OK Relay Mode

0

3

70

Sensor Temperature Set-point

0

45

71

Sensor Temperature Modulation

0

10

72

Period A

1

300

74 ~ 83

Cell b/m/n/s/a1/a2/a3/a4/a5/a6

-32767

32768

94

Sensor Serial Number

0

1000000

95

Program Revision

0

0

96

Please Wait

0

1

101 ~ 102

Service V/U

0

1

106

H201Ti ID(do not overwrite)

1

254

107

Power Station ID(do not overwrite)

1

9999

108

Baud Rate(do not overwrite)

0

3

109

Actual Computed Temperature Set-point

0

0

114 ~ 115

Long-term Log Point No. 1 Hour/Minute

0

23/59

116 ~ 117

Long-term Log Point No. 2 Hour/Minute

0

23/59

118 ~ 119

Long-term Log Point No. 3 Hour/Minute

0

23/59

120 ~ 121

Long-term Log Point No. 4 Hour/Minute

0

23/59

122 ~ 123

Hourly/Daily Trend Alarm Delay Percent

0

100

126

Analog Mode

0

3

127

TDM Mode

0

3

128

Analog Status

0

0

129

TDM Status

0

0

130

Comm Mode(do not overwrite)

0

1

131

Cell Parameters Check-sum

0

99999

133

Sensor Test Result

0

0

141

Service F

0

0

144

Full Scale(in ppm)

0

50000

<Table 2> Data number and contents of System Variable(5, 6 command)

Data number

Contents

0 ~ 1

Gas Set-Point Low Low/Low Active

2 ~ 3

Gas Set-Point High/High High Active

4 ~ 5

Hourly Set-Point Low Low/Low Active

6 ~ 7

Hourly Set-Point High/High High Active

8 ~ 9

Daily Set-Point Low Low/Low Active

10 ~ 11

Daily Set-Point High/High High Active

12 ~ 13

Sensor Temperature Set-Point Low Low/Low Active

14 ~ 15

Sensor Temperature Set-Point High/High High Active

16 ~ 17

Battery Set-Point Low Low/Low Active

18

Battery Set-Point High Active

24 ~ 25

Gas Set-Point Low Low/Low Fault Trigger

26 ~ 27

Gas Set-Point High/High High Fault Trigger

28 ~ 29

Hourly Set-Point Low Low/Low Fault Trigger

30 ~ 31

Hourly Set-Point High/High High Fault Trigger

32 ~ 33

Daily Set-Point Low Low/Low Fault Trigger

34 ~ 35

Daily Set-Point High/High High Fault Trigger

36 ~ 37

Sensor Temperature Set-Point Low Low/Low Fault Trigger

38 ~ 39

Sensor Temperature Set-Point High/High High Fault Trigger

40 ~ 41

Battery Set-Point Low Low/Low Fault Trigger

43

Set-up Lost Fault Trigger(version 2.2)

44

Sensor Test Set Short Cable Fault Trigger

45

Sensor Test Replace Sensor Soon Fault Trigger

46

Sensor Test Replace Sensor Now Fault Trigger

47

Sensor Test Open Cable Fault Trigger

48 ~ 50

Historic Long-term Log Point No.2 ~ 4 Active

<Table 3> Data number and contents of System Boolean(7, 8 command)

HYDRAN 201Ti communication driver store the same data in WORD, DWORD, FLOAT memory, but the data format are different.

If you click the icon  in protocol option part, you can see the dialogue box such as <Figure 2>. you can also set read schedule by using this part. 

<Figure 2> Example of HYDRAN 201Ti communication driver¡¯s Option dialogue box

You can set read schedule by using , , button and listbox of <Figure 2>. 

<Figure 3> Example of HYDRAN 201Ti communication driver¡¯s read schedule Add/Edit dialogue box

When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.

 

2. Writing settings

You can set HYDRAN 201Ti controller by using write settings

 

Digital Write

Digital write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION              0 ~ 254 controller station(address) number. 0 = Nobody Listens, 255 = Everybody listens(broadcast).

3)  ADDRESS           Decimal unit reading or writing address according to Extra1. ( refer to <Table 2>, <Table 3> )

4)  Extra1                   Read/Write command = 0 ~ 31. (refer to <Table 1> ) Default command = 7.

5)  Extra2                   Don't care.

 

 

Write example 1)

PORT:0,  station:1, ADDRESS:0000, Extra1: 7,  Extra2 :

The setting parameter shown above is 'Gas Set-point Low Low Active status'( refer to <Table 3> ) control(0 = OFF, 1 = ON) example of 1 station HYDRAN 201Ti  controller.

 

Write example 2)

PORT:0,  station:1, ADDRESS:0001, Extra1: 7,  Extra2 :

The setting parameter shown above is 'Gas Set-point Low Active status'( refer to <Table 3> ) control(0 = OFF, 1 = ON) example of 1 station HYDRAN 201Ti  controller.

 

 

Analog Write

Analog write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION              0 ~ 254 controller station(address) number. 0 = Nobody Listens, 255 = Everybody listens(broadcast).

3)  ADDRESS           Decimal unit reading or writing address according to Extra1. ( refer to <Table 2>, <Table 3> )

4)  Extra1                   Read/Write command = 0 ~ 31. (refer to <Table 1> ) Default command = 5.

5)  Extra2                   Decimal point.  ( 0 = 2 decimal point )

 

Write example 1)

PORT:0,  station:1, ADDRESS:0000, Extra1: 5,  Extra2 :

The setting parameter shown above is 'Gas ppm value'( refer to <Table 3> ) setting(2 decimal point unit) example of 1 station HYDRAN 201Ti  controller.

 

Write example 2)

PORT:0,  station:1, ADDRESS:0006, Extra1: 5,  Extra2 :

The setting parameter shown above is 'Hourly Set-Point High Active'( refer to <Table 3> ) setting(2 decimal point unit) example of 1 station HYDRAN 201Ti  controller.

 

3. Connectoin of communication cable and main power

 Connection of communication cable and main power line are as follows.

 

Connection of communication cable

Please connect normal RS-232C(cross) communication cable to 9 pin connector of  HYDRAN 201Ti  controller such as <Figure 4>.

<Figure 4> Connection example of main power and communication cable to HYDRAN 201T controller

Connection of main power

Please connect 230(220)V AC main power to L, N connector.

<Figure 5> is appearance of  HYDRAN 201Ti controller.

 

<Figure 5> Appearance of  HYDRAN 201Ti controller