HSCP communication driver is the driver to communicate with normal controller of Autobase Inc. in Korea.
<Figure 1> is read setting example of HSCP communication driver.
<Figure 1> Read setting example of HSCP communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(19200), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to setting of controller.
HSCP communication driver read schedule
Read schedule setting parameters are as follows:
1) Station – 0 ~ 255 station number of controller.
2) Device memory type – memory type = DI, DO, AI, AO
3) Read Start Address – Reading start address in device memory.
4) Save start address for Communication Server – Saving start address of Communication Server.
5) Read Size – Word unit read size.
Read schedule example)
READ, 0, DI, 0, 0, 2,
READ, 0, DO, 0, 2, 2,
READ, 0, AI, 0, 4, 16,
READ, 0, AO, 0, 20, 16,
You can set controller by using write settings.
Digital Write
Digital write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION 0 ~ 255 station number of controller.
3) ADDRESS Writing address of device type.
4) Extra1 Write device type = DO, AO.
5) Extra2 Don't care.
Write example 1)
PORT:0, station:1, ADDRESS:0003, Extra1:DO, Extra2 :
The setting parameter shown above is a bit control(On/Off) example for 0(1st) Word, 3(4th) bit.
Analog Write
Analog write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION 0 ~ 255 station number of controller.
3) ADDRESS Writing address of device type.
4) Extra1 Write device type = DO, AO.
5) Extra2 Don't care.
Write example 1)
PORT:0, station:1, ADDRESS:0015, Extra1:AO, Extra2 :
The setting parameter shown above is setting example for 15 Word memory of AO device.