Nuri GDC communication driver is the driver to communicate with GDC power demand controller of Nuri Control System in Korea.
<Figure 1> is read setting example of Nuri GDC communication driver.
<Figure 1> Read setting example of Nuri GDC communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(19200), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively according to setting of controller.
Nuri GDC communication driver read schedule
Read schedule setting parameters are as follows:
1) STATION – Don't care.
2) Read command – Command = A, B, C, D, E, F, G, H, I.
3) Read start address – Fixed to 0.(Don't care)
4) Save Start Address for Communication Server – saveing start address of Communication Server.
5) Read Size – Fixed according to read command.
Read schedule example)
FLOAT, 0, A, 0, 0, 33,
FLOAT, 0, B, 0, 35, 25,
FLOAT, 0, C, 0, 60, 21,
FLOAT, 0, D, 0, 85, 29,
FLOAT, 0, E, 0, 115, 29,
FLOAT, 0, F, 0, 145, 14,
FLOAT, 0, G, 0, 160, 14,
FLOAT, 0, H, 0, 175, 10,
FLOAT, 0, I, 0, 185, 19,
Read size according to read command)
A : 33
B : 25
C : 21
D : 29
E : 29
F : 14
G : 14
H : 10
I : 19
<Table 1> is contents and data range for A read command.
Order | Contents | Byte size | Range |
01 |
Current year | 1 |
0 ~ 99 |
02 |
Current day of the week | 1 |
1 ~ 7 |
03 |
Current month | 1 |
1 ~ 12 |
04 |
Current day | 1 |
1 ~ 31 |
05 |
Current hour | 1 |
0 ~ 23 |
06 |
Current minute | 1 |
0 ~ 59 |
07 |
Current second | 1 |
0 ~ 59 |
08 |
DI remain minute | 1 |
0 ~ 15 |
09 |
DI remain second | 1 |
0 ~ 59 |
10 |
Using power progress | 3 |
0 ~ 999999 |
11 |
The target power progress | 3 |
0 ~ 999999 |
12 |
Alarm power progress | 3 |
0 ~ 999999 |
13 |
Adjust the power -/+ | 1 |
0 ~ 1 |
14 |
Adjust the power | 3 |
0 ~ 999999 |
15 |
Current power | 3 |
0 ~ 999999 |
16 |
W1 current power | 3 |
0 ~ 999999 |
17 |
W2 current power | 3 |
0 ~ 999999 |
18 |
Demand power | 3 |
0 ~ 999999 |
19 |
Maximum power | 3 |
0 ~ 999999 |
20 |
Maximum power of month | 1 |
1 ~ 12 |
21 |
Maximum power of day | 1 |
1 ~ 31 |
22 |
T sum | 4 |
0 ~ 99999999 |
23 |
T op | 4 |
0 ~ 99999999 |
24 |
T p | 4 |
0 ~ 99999999 |
25 |
T n | 4 |
0 ~ 99999999 |
26 |
Mon sum | 4 |
0 ~ 99999999 |
27 |
Mon op | 4 |
0 ~ 99999999 |
28 |
Mon p | 4 |
0 ~ 99999999 |
29 |
Mon n | 4 |
0 ~ 99999999 |
30 |
Load control state | 1 |
0 ~ FF |
31 |
Full scale | 3 |
0 ~ 999999 |
32 |
Time zone alarm power | 3 |
0 ~ 999999 |
33 |
Shut-off power | 3 |
0 ~ 999999 |
<Table 1> Contents and data range for A read command |
Nuri GDC communication driver don't support 'write settings'.