FUJI MICREX-F ENET communication driver

 

FUJI MICREX-F ENET communication driver is the driver to communicate with ethernet module PLC((120S ~ 150S, 120H ~ 150H) of Fuji Electric Co., Ltd. in Japan.

 

Note) For communicate with ethernet module of FUJI MF series PLC, you have to make Ladder routine for setting of ethernet communication. 

Reference : PLC setting for using FUJI MICREX-F ENET communication driver

 

1. Read settings

 

<Figure 1> is read setting example of FUJI MICREX-F ENET communication driver. 

<Figure 1>  Read setting example of  FUJI MICREX-F ENET communication driver

Device part of  <Figure 1> input Device type(TCP/IP or UDP/IP), IP address of PLC(192.168.0.2), service port of TCP/IP(UDP/IP) protocol (2000 ),respectively, according to setting of PLC.

 

Note) When a communication error about TCP/IP connection occurs, the problem can be solved as follows.

1) Make 2 or more TCP/IP (or UDP/IP) service port routine in the Ladder program.

2) Input service port number at 'Device' part of <Figure 1> such as 2000, 2011, 2002 ¡¦(service port number = made by ladder program).

3) It can slove TCP/IP connection problem by connecting the next service port.

 

FUJI MICREX-F ENET communication driver read schedule

Read schedule setting parameters are as follows:

1) STATION – Don't care.

2) Read command – Read memory type or command = B, M, K, F, A, D, W9, TS, TR, CS, CR, BD, WL, WL2, WB, Wm, WK, WA, WD, W21. (  Refer to <Table 1>, <Table 2> )

3) Read start address – Read start address in memory type = 0 ~  .

4) Save Start Address for Communication Server – saveing start address of Communication Server.

5) Read Size – Read size of Byte,Word, Dword unit = Byte : 1 ~ 212, Word 1 ~ 106, Dword : 1 ~ 53.

 

Read schedule example)

READ,     0,     B,     0,    0,   16,

READ,     0,     M,     0,   16,  16,

READ,     0,   WD,     0,  32,  16,

READ,     0,   WA,     0,  48,  16,

DWORD, 0,   W9,     0,   0,  50,

DWORD, 0,   BD,     0,  50,  50,

 

<Table 1> is memory type and data form of FUJI MICREX-F ENET communication driver.

<Table 2> is memory type and read/write command of FUJI MICREX-F ENET communication driver.

Memory type Data form Remarks

B

WORD  

Digital input/output area

M

WORD  

Internal memory area

K

WORD  

 

F

WORD  

 

A

WORD  

 

D

WORD  

 

W9

DWORD

 

TS

DWORD

 

TR

DWORD

 

CS

DWORD

 

CR

DWORD

 

BD

DWORD

 

WL

WORD  

Bit type of WL memory area

WB

BCD_WORD

Get 16 bit BCD value at B memory area

WM

BCD_WORD

Get 16 bit BCD value at M memory area

WK

BCD_WORD

Get 16 bit BCD value at K memory area

WF

BCD_WORD

Get 16 bit BCD value at F memory area

WA

BCD_WORD

Get 16 bit BCD value at A memory area

WD

BCD_WORD

Get 16 bit BCD value at D memory area
<Table 1> Memory type and data form of FUJI MICREX-F ENET communication driver
Device Memory type Contents Read/Write command Address range (when 120S : decimal) Remarks
B Input, output relay B 0 ~ 511 Bit Address, WORD unit
WB WORD
M Auxiliary relay M Bit Address, WORD unit
WM WORD
K Keep relay K 0 ~ 63 Bit Address, WORD unit
WK WORD
F Special relay F 0 ~ 125 Bit Address, WORD unit
WF WORD
A Annunciate relay A 1 ~ 45 Bit Address, WORD unit
WA WORD
D Differential relay D 0 ~ 63 Bit Address, WORD unit
WD WORD
S Step control WS 0 ~ 99 BYTE ( 8 Bit )
W9 Current value of 0.1second timer W9 0 ~ 511 DWORD
TS Setting value of timer TS
TR Current value of timer TR
CS Setting value of counter CS
CR Current value of counter CR
BD Data memory BD 0 ~ 255
WL 0 station 1 block memory of P-Link memory WL 0 ~ 4095 WORD
W21 0 station 2 block memory of P-Link memory W21
W22 0 station 3 block memory of P-Link memory W22
W23 0 station 4 block memory of P-Link memory W23
W24 Direct input, output I/O W24 0 ~ 127
W25 Analog work area W25 0 ~ 511 DWORD
W26 Old value of differential relay W26 0 ~ 63 WORD
W120 1 station 1 block memory of P-Link memory W120 0 ~ 4095
W121 1 station 2 block memory of P-Link memory W121
W122 1 station 3 block memory of P-Link memory W122
W123 1 station 4 block memory of P-Link memory W123
W125 Calendar area W125 0 ~ 5
CAL
W30 ~W109 File memory FILE30 ~ 109 0 ~ 4095 WORD
FILED30 ~ 109 DWORD
<Table 2> Memory type and read/write command of FUJI MICREX-F ENET communication driver

If you click the icon  in protocol option part, you can see the dialogue box such as <Figure 2>. you can also set read schedule by using this part.

<Figure 2> Example of FUJI MICREX-F ENET communication driver¡¯s Option dialogue box

You can set read schedule by using , , button and listbox of <Figure 2>. 

<Figure 3> Example of FUJI MICREX-F ENET communication driver¡¯s read schedule Add/Edit dialogue box

When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.

 

2. Write settings

You can change the value of device memory by using write settings.

 

Digital Write

Digital write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             Don't care.

3)  ADDRESS          Write addres in memory type.

Byte unit device memory(WS, ...) : higher 3 ~ 7 digit = byte unit address,  lower 1 digit = 0 ~ 7 bit position,

Word unit device memory :  higher 3 ~ 7 digit = word unit address,  lower 1 digit = 0 ~ F bit position,

Dword unit device memory :  higher 3 ~ 7 digit = dword unit address,  lower 1 digit = 0 ~ F bit position, 10h ~ 1Fh bit position = value of Extra2(0 ~ 1). 

4) Extra1                   Write memory type = B, WB, M, WM, K, WK, F, WF, A, WA, D, WD, WS, W9, TS, TR, CS, CR, BD, WL, W21, W22, W23, W24, W25, W26, FILE30 ~ 109, FILED30 ~ 109, W120, W121, W122, W123, W125, CAL (Refer to <Table 2>)

5) Extra2                   Higher bit position when Dword unit device memory.

W9, TS, TR, CS, CR, BD, W25,... Dword device memory : 0 = 0h ~ Fh bit position,  1 = 10h ~ 1Fh bit position,

other device memory : don't care.

 

Note) Word, Dword unit device memory don't support digital(bit) unit write protocol.

So FUJI FC Series CCS communication driver made digital write by 'bit operation method' after reading the word, dword memory. 

When the 'digital output', B-WB, M-WM, K-WK, F-WF, A-WA, D-WD device memory equal area, but bit position is opposite such as <Table 3>.

(B, M, K, F, A, D Device memory's bit address and word address have inverse bit position)

 Example) M0  =  1F23h,  WM0 = C4F8h

 

Normally Digital read/wirite use B, M, K, F, A, D command, Analog read/wirite use WB, WM, WK, WF, WA, WD command.

Device type Bit position
WB, WM, WK, WF, WA, WD,... 0 1 2 3 4 5 6 7 8 9 A B C D E F
B, M, K, F, A, D,... F E D C B A 9 8 7 6 5 4 3 2 1 0
<Table 3> Bit position acoording to device type

Write example 1)

PORT:0,  station:0, ADDRESS:001A, Extra1: M,  Extra2 :

The setting parameter shown above is a bit write(On/Off) example of  M001A(A bit, 1 word) in the M device memory.

 

Write example 2)

PORT:0,  station:0, ADDRESS:0100, Extra1: M,  Extra2 :

The setting parameter shown above is a bit write(On/Off) example of  M0100(0 bit, 10 word) in the M device memory.

 

Write example 3)

PORT:0,  station:0, ADDRESS:012F, Extra1: BD,  Extra2 : 0

The setting parameter shown above is a bit write(On/Off) example of  F(16th) bit, 12(13th) dword in the BD device memory.

 

Write example 4)

PORT:0,  station:0, ADDRESS:012F, Extra1: BD,  Extra2 : 1

The setting parameter shown above is a bit write(On/Off) example of  1F(32th) bit, 12(13th) dword in the BD device memory.

 

Analog Write

Analog write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             Don't care.

3)  ADDRESS          Word unit addres in memory type.

4) Extra1                   Write memory type = B, WB, M, WM, K, WK, F, WF, A, WA, D, WD, WS, W9, TS, TR, CS, CR, BD, WL, W21, W22, W23, W24, W25, W26, FILE30 ~ 109, FILED30 ~ 109, W120, W121, W122, W123, W125, CAL (Refer to <Table 2>)

5) Extra2                    Don't care.

 

 Write example 1)

PORT:0,  station:0, ADDRESS:0000, Extra1: WM,  Extra2 :

The setting parameter shown above is an word write example of  0(1st) word in the M device memory.

 

 Write example 2)

PORT:0,  station:0, ADDRESS:0015, Extra1: WD,  Extra2 :

The setting parameter shown above is an word write example of  15(16th) word in the D device memory.

 

 Write example 3)

PORT:0,  station:0, ADDRESS:0031, Extra1: BD,  Extra2 :

The setting parameter shown above is an double word write example of  31(32th) double word in the BD device memory.

 

 Write example 3)

PORT:0,  station:0, ADDRESS:0125, Extra1: W9,  Extra2 :

The setting parameter shown above is an double word write example of  125(126th) double word in the W9 device memory.