FREQROL 500 Series Inverter communication driver

 

 

FREQROL 500 Series Inverter communication driver is the driver to communicate with inverter controller of Mitsubishi Electric Corporation in Japan.

 

1. Read settings

 

<Figure 1> is read setting example of  FREQROL 500 Series Inverter communication driver. 

<Figure 1>  Read setting example of  FREQROL 500 Series Inverter communication driver

Device part of  <Figure 1> input Com Port(COM1), Baud Rate(19200), Parity Bit(2), Data Bit(8), Stop Bit(2) respectively according to setting of controller.

Baud rate(4800, 600, 1200, 2400,4800, 9600, 19200), parity bit(0, 1, 2), stop bit(1, 2) can set by using 'setting button' of FREQROL 500 Series.

Also you can input 'enable of Link Parameter Expansion's auto setting' (1 : enable, 0 : disable, default = 1), 'type of communication end code'(0 : none, 1 : CR, 2 : CR+LF, default = 1), 'use of Waiting Time in Protocol'(1 : use, 0 : don't use : 0, default = 1), 'Waiting Time when using Waiting Time'(0 ~ 15, unit = 10ms, default = 1), 'send of ACK packet after reading'(1 : send, 0 : don't send : 0, default = 0)  by using option part.

 

Note) When Instruction number of 30(Extended function display selection) = 0(break - MRS type) , the usable Instruction number are 0 ~ 9, 30, 79 ...

Note) Please refer to 4 chapter for setting of controller's station number, baud rate, etc.

 

FREQROL 500 Series Inverter communication driver read schedule

Read schedule setting parameters are as follows:

1) STATION – Controller's station number = 0 ~ 31.

2) Link Parameter Expansion – Expansion number = 0 ~ 9. (  Refer to <Table 1> or reference manual of FREQROL 500 Series Inverter )

3) Instruction  number – Read Instruction number = 0 ~ 127.  (  Refer to <Table 1> or reference manual of FREQROL 500 Series Inverter )

4) Save Start Address for Communication Server – saveing start address of Communication Server.

5) Read Size – read word size = fixed to 1.

 

Read schedule example)

READ,     0,     0,    1h,    0,   1,

READ,     0,     0,    2h,    1,   1,

READ,     0,     0,    3h,    2,   1,

READ,     0,     0,    4h,    3,   1,

READ,     0,     0,    5h,    4,   1,

READ,     0,     0,    6h,    5,   1,

READ,     0,     0,    7h,    6,   1,

READ,     0,     0,   1Dh,    7,   1,

READ,     0,     0,   1Eh,    8,   1,

READ,     0,     0,   1Fh,    9,   1,

 

 

Please refer to reference manual of FREQROL 500 Series Inverter for readed data value and contents.

If you click the icon  in protocol option part, you can see the dialogue box such as <Figure 2>. you can also set read schedule by using this part.

<Figure 2> Example of  FREQROL 500 Series Inverter communication driver¡¯s Option dialogue box

You can set read schedule by using , , button and listbox of <Figure 2>. 

Also you can set enable of Link Parameter Expansion's auto setting, type of communication end code, use of Waiting Time in Protocol, Waiting Time, send of ACK packet after reading at the part of ¡®Communication Option¡¯ shown in <Figure 2>.

<Figure 3> Example of  FREQROL 500 Series Inverter communication driver¡¯s read schedule Add/Edit dialogue box

When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.

 

2. Write settings

You can write setting value of inverter by using write settings.

 

Digital Write

Digital write and Analog write have the same setting parameters except output value(0 or 1).

 

Analog Write

Analog write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             Controller station number = 1 ~ 31.

3)  ADDRESS           Write Instruction number = 0 ~ 127( or 128 ~ 255, decimal unit).  (  Refer to <Table 1> or reference manual of FREQROL 500 Series Inverter )

4) Extra1                    Expansion number = 0 ~ 9. (  Refer to <Table 1> or reference manual of FREQROL 500 Series Inverter )

5) Extra2                    Number of writing bytes.(default = 2)

                          1 : 1 byte data,

                           3 : 3 byte data,

                           2, space, ... : 2 byte data. (default)

 

Note) In order to write some Instruction number, you should be set 'EXT' mode of Inverter's communication mode.

Also when the 77 Instruction number's value equal 1 or 0 and PU operation mode equal don't stop, you can't set most of the parameter. (you can set 75, 77, 79, .. Instruction parameters)

But you can set parameter when the 77 Instruction number's value equal 2 regardless of PU mode.

 

Write example 1)

PORT:0,  station:0, ADDRESS:0001, Extra1: 0,  Extra2 :

The setting parameter shown above is maximum frequency setting example of  0 station FREQROL 500 Series Inverter.

 

Write example 2)

PORT:0,  station:0, ADDRESS:0002, Extra1: 0,  Extra2 :

The setting parameter shown above is minimum frequency setting example of  0 station FREQROL 500 Series Inverter.

 

3. connection of communication cable and main power

Connection of communication cable and main power are as follows.

 

Connection of communication cable

Please connect RS-485 communication cable to RS-485 connector of FREQROL 500 Series Inverter such as <Figure 4>.

PU connector of FREQROL 500 Series       RS-485 connector of computer

3  connector(RDA) -------------------------------------------- SDA(T+)

4 connector (SDB) -------------------------------------------- RDB(R-)

5 connector (SDA) -------------------------------------------- RDA(R+)

6 connector (RDB) -------------------------------------------- SDB(T-)

<Figure 4> RS-485 communication cable daigram between  FREQROL 500 Series Invert(PU connector) amd computer

 

<Figure 5> is connection example of  communication cable and main power to FREQROL 500 Series Inverter.

<Figure 5> Connection example of  communication cable and main power to FREQROL 500 Series Inverter

Connection of main power

Please connect 220V AC or 3 phase power to R.S.T such as <Figure 5>.

<Figure 6> is appearence of FREQROL 500 Series Inverter.

<Figure 6> Appearence of FREQROL 500 Series Inverter
4. Setting of controller station address and baud rate

 

You can set controller station address, baud rate, ... by using front panel' setting button of FREQROL 500 Series inverter.

Also you can set by using write settings.

 

 Note) After setting the controller station, baud rate, etc, you have to reset(power reset or reset command) the controller.

 

 Setting of controllser station number

Controller station number can be set as follows:

 1) Press 'MODE' button at normal operation status. Then will display 'Instruction(P0 ~ P127, n0 ¡¦ ) at the screen.

2) Please set 'n1 Instruction' by using dial switch.

3) Press 'SET' button, then will display current setting station number.

4) Set the station what you want by using dial switch.

5) After setting the station, press 'SET' button.

6) Press 'MODE' button 2 times, then will goes back to the normal operation status.

 

 Setting of baud rate

Baud rate number can be set as follows:

1) Press 'MODE' button at normal operation status. Then will display 'Instruction(P0 ~ P127, n0 ¡¦ ) at the screen.

2) Please set 'n2 Instruction' by using dial switch.

3) Press 'SET' button, then will display current setting baud rate(48, 96, 192, etc).

4) Set the baud rate what you want by using dial switch.

5) After setting the baud rate, press 'SET' button.

6) Press 'MODE' button 2 times, then will goes back to the normal operation status.

 

Setting of extended function display selection

Extended function display selection number can be set as follows:

1) Press 'MODE' button at normal operation status. Then will display 'Instruction(P0 ~ P127, n0 ¡¦ ) at the screen.

2) Please set 'P 30 Instruction' by using dial switch.

3) Press 'SET' button, then will display current setting extended function display selection(0 or 1).

4) Set the extended function display selection what you want by using dial switch.

5) After setting the extended function display selection, press 'SET' button.

6) Press 'MODE' button 2 times, then will goes back to the normal operation status.

 

Setting of communication End Code

Communication End Code can be set as follows:

1) Press 'MODE' button at normal operation status. Then will display 'Instruction(P0 ~ P127, n0 ¡¦ ) at the screen.

2) Please set 'n 11 Instruction' by using dial switch.

3) Press 'SET' button, then will display current setting communication End Code(0, 1, 2).

4) Set the communication End Code what you want by using dial switch( 0 = none, 1 = CR, 2 = CR+LF ).

5) After setting the communication End Code, press 'SET' button.

6) Press 'MODE' button 2 times, then will goes back to the normal operation status.

 

Setting of waiting time

Waiting time can be set as follows:

1) Press 'MODE' button at normal operation status. Then will display 'Instruction(P0 ~ P127, n0 ¡¦ ) at the screen.

2) Please set 'n 7 Instruction' by using dial switch.

3) Press 'SET' button, then will display current setting waiting time(0 ~ 150 or 65535).

4) Set the waiting time what you want by using dial switch(0 ~ 150 or etc).

5) After setting the waiting time, press 'SET' button.

6) Press 'MODE' button 2 times, then will goes back to the normal operation status.

 

Note) When Instruction number of 30(Extended function display selection) = 0(break - MRS type) , the usable Instruction number are 0 ~ 9, 30, 79 ... and can't set controller station, baud rate, etc.

If you want to set controller station, baud rate, etc, you have to set 'Extended function display selection' = 1.

 

5. Instruction number of FREQROL 500 Series Inverter

<Table 1> is a Instruction number, Link Parameter Expansion number and contents of  FREQROL 500 Series Inverter.

 

 

<Table 1> Instruction number, Link Parameter Expansion number and contents of  FREQROL 500 Series Inverter