ECU-09 Micom Controller Communication Driver

 

ECU-09 Micom Controller communication driver is the driver to communicate with temperature chamber controller of Nemo Engineering. in Korea.

 

1. Read settings

 

<Figure 1> is read setting example of  ECU-09 Micom Controller communication driver. 

<Figure 1>  Read setting example of  ECU-09 Micom Controller communication driver

Device part of  <Figure 1> input Com Port(COM1), Baud Rate(fixed to 9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to setting of controller.

 

Note) Please set the 'read cycle' more than 200(mSec unit). If you set under 200, the keypad of temperature chamber controller does not operate normally.

 

ECU-09 Micom Controller communication driver¡¯s read schedule

Read schedule setting parameters are as follows:

1) Station – Controller station number = 1 ~ 32.

2) Read Type – Don't care.

3) Read Start Address Don't care.

4) Save start address for Communication Server – Saving start address of Communication Server.

5) Read Size – fixed to 1. ( Refer to <Table 1> )

 

Read schedule example) 

READ,     1,     ,     0,    0,   1,

 

<Table 1> is data saving address and contents of ECU-09 Micom Controller communication driver.

Data Saving Address Contents Remarks
When 2 compressor When 3 compressor
Start Add + 0 Ooperation status of temperature chamber controller BIT0 : operation status
Start Add + 1 Current temperature Real value = read value / 2
Start Add + 2 Setting temperature Real value = read value / 2
Start Add + 3 Induction temperature Real value = read value / 2
Start Add + 4 Current humidity Real value = read value / 2
Start Add + 5 Setting humidity Real value = read value / 2
Start Add + 6 Induction humidity Real value = read value / 2
Start Add + 7 Operation delay time of compressor  
Start Add + 8  High alarm setting temperature Real value = read value / 2
Start Add + 9 Start time of drainage  
Start Add + 10 Stop delay time of air blower  
Start Add + 11   Don't care
Start Add + 12 Restart time of equipment  
Start Add + 13 Auto alternation time of compressor  
Start Add + 14   Don't care
Start Add + 15 Operation status of FAN OUT BIT0 : operation status
Start Add + 16   Don't care
Start Add + 17 Operation status of compressor 1 BIT0 : operation status
Start Add + 18   Don't care
Start Add + 19 Operation status of compressor 2 BIT0 : operation status
Start Add + 20 Operation status of heater 1 BIT0 : operation status
Start Add + 21 Operation status of heater 2 BIT0 : operation status
Start Add + 22 Operation status of heater 3 BIT0 : operation status
Start Add + 23 Operation status of heater 4 BIT0 : operation status
Start Add + 24 Operation status of heater 5 Operation status of compressor 3 BIT0 : operation status
Start Add + 25 Operation status of humidification 1 BIT0 : operation status
Start Add + 26 Operation status of humidification 2 BIT0 : operation status
Start Add + 27 Operation status of watering BIT0 : operation status
Start Add + 28 Operation status of drainage BIT0 : operation status
Start Add + 29 Operation status of cooling BIT0 : operation status
Start Add + 30 Operation status of dehumidification BIT0 : operation status
Start Add + 31 Abnormal of FAN BIT0 : operation status
Start Add + 32 Abnormal of compressor 1 BIT0 : operation status
Start Add + 33 Abnormal of compressor 2 BIT0 : operation status
Start Add + 34 Abnormal of heating BIT0 : operation status
Start Add + 35 Abnormal of humidification BIT0 : operation status
Start Add + 36 Abnormal of sensor BIT0 : operation status
Start Add + 37 Abnormal of water leaks Abnormal of compressor 3 BIT0 : operation status
Start Add + 38 High temperature status BIT0 : operation status
Start Add + 39   Don't care
Start Add + 40 Fire alarm BIT0 : operation status
Start Add + 41 Abnormal of water sensing BIT0 : operation status
Start Add + 42 Remote control operation BIT0 : operation status
Start Add + 43   Don't care
<Table 1> Data Saving Address and contents of ECU-09 Micom Controller communication driver
2. Writing settings

You can write the setting value by using write settings.

 

Digital Write

Digital write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             Controller station number = 1 ~ 32.

3)  ADDRESS           Don't care.

4)  Extra1                   Write command = CONT : control command.

5)  Extra2                   Don't care.

 

Write example 1) 

Port : 0,  Station : 1,  Address : 0000,  EXTRA1 : CONT,  EXTRA2 : 0

The setting parameter shown above is a control(On/Off) example of 1 controller station number 

 

Analog Write

Analog write setting parameters are as follows:

1)  PORT                   Port no. (0 ~ 255)

2)  STATION             Controller station number = 1 ~ 32.

3)  ADDRESS           Don't care.

4)  Extra1                   Write command.

TEMP : Increase(+) or decrease(-) of setting temperature,

STEMP : Increase(+) or decrease(-) of induction temperature,

HUMI :  Increase(+) or decrease(-) of setting humidity,

SHUMI : Increase(+) or decrease(-) of induction humidity,

PUMDLY : Increase(+) or decrease(-) of compressor operation delay time,

ALMTEM : Increase(+) or decrease(-) of high temperature alarm setting,

FANDLY : Increase(+) or decrease(-) of fan delay stop time,

PUMEXC : Increase(+) or decrease(-) of compressor auto alternating hours. 

5)  Extra2                   Don't care.

 

Write example 1) 

Port : 0  Station : 1  Address : 0000  EXTRA1 : TEMP  EXTRA2 : 0

The setting parameter shown above is a write example of setting temperature(increase or decrease). 

 

Write example 2) 

PORT : 0   STATION : 1   ADDRESS : 0000  EXTRA1 : STEMP  EXTRA2 : 0

The setting parameter shown above is a write example of induction temperature(increase or decrease). 

 

Write example 3) 

PORT : 0   STATION : 1   ADDRESS : 0000  EXTRA1 : HUMI  EXTRA2 : 0

The setting parameter shown above is a write example of setting humidity(increase or decrease). 

 

Write example 4) 

PORT : 0   STATION : 1   ADDRESS : 0000  EXTRA1 : SHUMI  EXTRA2 : 0

The setting parameter shown above is a write example of induction humidity(increase or decrease). 

 

Write example 5) 

PORT : 0   STATION : 1   ADDRESS : 0000  EXTRA1 : PUMDLY  EXTRA2 : 0

The setting parameter shown above is a write example of compressor operation delay time(increase or decrease). 

 

Write example 6) 

PORT : 0   STATION : 1   ADDRESS : 0000  EXTRA1 : ALMTEM  EXTRA2 : 0

The setting parameter shown above is a write example of high temperature alarm setting(increase or decrease). 

 

Write example 7) 

PORT : 0   STATION : 1   ADDRESS : 0000  EXTRA1 : FANDLY  EXTRA2 : 0

The setting parameter shown above is a write example of fan delay stop time(increase or decrease). 

 

Write example 8) 

PORT : 0   STATION : 1   ADDRESS : 0000  EXTRA1 : PUMEXC  EXTRA2 : 0

The setting parameter shown above is a write example of compressor auto alternating hours(increase or decrease). 

 

3. connection of main power line and communication cable

 Connection of main power line and communication cable are as follows.

 

Connection of main power line

Please connect main power to  connector AC, COM220, 220V AC. 

 

Connection of communication cable

Please connect ECU-09 controller¡¯s RS-485 X+,X- connector and computer's RS-485 +, - connector respectively.

   ECU-09 controller's 485 connector      Computer's RS-485 connector

                X+  ---------------------------------------------------  +

                X-  ----------------------------------------------------  -

 

<Figure 2> is connection example of main power line and RS-485 communication cable to ECU-09 controller.

<Figure 2> Connection example of main power line and RS-485 communication cable to ECU-09 controller